4 TROUBLESHOOTING
4.5 List of Error Codes
C053H
The number of read/write points from/to the
random device of SLMP message is out of
the allowable range in the CPU module (in
units of bits).
Correct the number of read/write points and send the SLMP message to the
CC-Link IE TSN-equipped module again.
C054H
The number of read/write points from/to the
random device of SLMP message is out of
the allowable range in the CPU module (in
units of words, double words).
Correct the number of read/write points and send the SLMP message to the
CC-Link IE TSN-equipped module again.
C055H
The read/write size from/to the file data of
SLMP message is out of the allowable
range.
Correct the read/write size send the SLMP message to the CC-Link IE TSN-
equipped module again.
C056H
The read/write request exceeds the largest
address.
• Correct the start address or the number of read/write points so that the
request does not exceed the largest address and send the data to the CC-
Link IE TSN-equipped module again.
• If the access target and connection stations are modules of the MELSEC
iQ-R series, send the SLMP message again to the CC-Link IE TSN-
equipped module using 00
3 and 00
2 of subcommands.
C057H
The request data length of the SLMP
message does not match the number of data
in the character (a part of text).
Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
C058H
The request data length of the SLMP
message after the ASCII/binary conversion
does not match with the number of data in
the character (a part of text).
Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
C059H
• The specified command and subcommand
of the SLMP message are incorrect
• A function that is not supported by the
target device was executed.
• Check that there are no errors in the specification of the command and
subcommand of the SLMP message.
• Check whether the function executed is supported by the target device.
• Check the version of the target device.
C05AH
The CC-Link IE TSN-equipped module
cannot read/write data from/to the device
specified by the SLMP message.
Correct the specification of the device to be read/written and send the SLMP
message to the CC-Link IE TSN-equipped module again.
C05BH
The CC-Link IE TSN-equipped module
cannot read/write data from/to the device
specified by the SLMP message.
Correct the specification of the device to be read/written and send the SLMP
message to the CC-Link IE TSN-equipped module again.
C05CH
The received request data of the SLMP
message is incorrect.
Correct the request data and send the SLMP message to the CC-Link IE
TSN-equipped module again.
C05DH
The "Monitor Request" command is received
before the monitor registration is performed
by the "Monitor Registration/Clear"
command of the SLMP message.
Register the monitoring data using "Monitor Registration/Clear" command
and perform monitoring.
C05EH
• The time between reception of the SLMP
message by the CC-Link IE TSN-
equipped module and the returned
response from the access destination
exceeded the monitoring timer value set in
the SLMP command.
• An unresponsive command was sent to
another network station as the access
destination. (If this error does not cause
any problems, it can be ignored.)
• Increase the monitoring timer value.
• Check if the access destination is operating normally.
• Correct the network number or request destination station number.
• If the access destination is a module with a different network number,
correct the routing parameter setting.
• If the access destination is a module with a different network number,
check if the network number is not in use.
C05FH
This request cannot be executed to the
access destination specified by the SLMP
message.
Correct the access destination.
C060H
The request details for bit devices of the
SLMP message is incorrect.
Correct the request details and send the SLMP message to the CC-Link IE
TSN-equipped module again.
C061H
• The request data length of the SLMP
message does not match the number of
data in the character (a part of text).
• The write data length specified by the
label write command is not even byte.
• Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
• Add one byte of dummy data, and specify the length as an even number
of bytes.
Error
code
Error definition and causes
Action
Detailed
information 1
Detailed
information 2