2 PARAMETER SETTINGS
2.4 Application Settings
Communication speed setting
Set the communication speed.
*1 This speed can be used for the firmware version "04" or later.
For details on the connection of modules or devices based on the communication speed setting, refer to the following.
MELSEC iQ-R CC-Link IE TSN User's Manual (Startup)
Supplementary Cyclic Settings
Set the station-based block data assurance and I/O maintenance settings.
Transient Transmission Group No. Setting
Set the transient transmission group number.
Communication Mode
Set the communication mode.
*1 This communication mode can be used for the firmware version "04" or later.
Parameter Name
Set a name for the module parameter if desired.
Item
Description
Setting range
Communication Speed
Select the communication speed.
• 1Gbps
• 100Mbps
(Default: 1Gbps)
Item
Description
Setting range
Station-based Block Data Assurance
Select whether to ensure a data integrity of the data blocks being
refreshed between the CPU module and the RJ71GN11-T2. (
Page 35 Cyclic data assurance)
• Enable
• Disable
(Default: Enable)
I/O Maintenance
Settings
Output Hold/Clear Setting during
CPU STOP
Select whether to hold or clear output when the status of the CPU
module changes from RUN to STOP. Set it on the sending side.
(
Page 44 I/O maintenance settings)
• Hold
• Clear
(Default: Hold)
Data Link Error Station Setting
Select whether to clear or hold input from a disconnected station.
Set it on the receiving side. (
• Clear
• Hold
(Default: Clear)
Output Mode upon CPU Error
Select whether to hold or clear output when a stop error occurs in
the CPU module. Set it on the sending side. (
• Clear
• Hold
(Default: Clear)
Item
Description
Setting range
Transient Transmission Group No.
Setting
Set the group number to perform transient transmission using group specification.
0 to 32 (0: No group
specification)
(Default: 0)
Item
Description
Setting range
Communication Mode
Set the communication mode.
• Unicast
• Multicast
(Default: Unicast)
Item
Description
Setting range
Parameter Name
Set a name for the module parameter if desired.
Up to 8 one-byte or two-byte
characters
(Default: empty)