APPX
Appendix 5 List of Link Special Register (SW)
275
A
SW0045
Module type
Stores the hardware status of the own station.
Model type
00: Module
01: Board
10: HMI (Human Machine Interface)
SW0046 to
SW0047
IPv4 address
Indicates the IP address (IPv4) set in the own station.
(1): Third octet
(2): Fourth octet
(3): First octet
(4): Second octet
SW0049
Cause of data
link stop
Stores the cause which stopped the data link of the own station.
00H: At normal communication or power-on
02H: Monitoring time timeout
05H: No slave station (master station only)
10H: Parameter not received (local station only)
11H: Outside the range of own station numbers
12H: Reserved station setting of own station (local station only)
14H: Master station duplication (master station only)
16H: Station number not set (local station only)
18H: Parameter error
19H: Parameter communication in progress
20H: CPU module moderate error, major error
60H: Illegal ring connection (master station only)
(Also used in the CLPA conformance test.)
(Updated even if set as an error invalid station.)
(Updated even if set as a reserved station.)
SW004B
CPU status of
own station
Stores the status of the CPU module on the own station.
00H: No CPU module mounted
01H: STOP (normal)
02H: STOP (moderate/major error)
03H: STOP (minor error)
04H: RUN (normal)
05H: RUN (minor error)
07H: PAUSE
0EH: Reset in progress
0FH: Initial processing in progress
SW004C
Parameter
setting status
Stores the status of parameter settings.
0: Normal
1 or greater: Error definition (Error code is stored.)
(Conditions)
• This register is enabled when 'Received parameter error' (SB004D) is on.
SW0058
Total number of
slave stations
setting value
Stores the total number of slave stations that are set by the parameters.
Range: 1 to 120
SW0059
Total number of
slave stations
present value
Stores the total number of slave stations that are actually connected by data link.
Range: 1 to 120 (0 when own station is disconnected)
Since a local station cannot obtain the station information of the CC-Link IE TSN
Class A remote station when communicating in multicast mode, the CC-Link IE
TSN Class A remote station is reflected as a station performing normal data link.
SW005B
Maximum data
link station
number
Stores the maximum station number of the station where the data link is normally
performed.
Range: 1 to 120 (0 when own station is disconnected)
Since a local station cannot obtain the station information of the CC-Link IE TSN
Class A remote station when communicating in multicast mode, the CC-Link IE
TSN Class A remote station is reflected as a station performing normal data link.
• This register is enabled when 'Data link error status of own station' (SB0049) is
off.
No.
Name
Description
Availability
Master
station
Local station
Unicast
mode
Multicast
mode
b15
b2 b1 b0
SW0045 0
0
to
to
SW0046
SW0047
(1)
(2)
(3)
(4)
Summary of Contents for MELSEC iQ-R CC-Link IE TSN
Page 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Page 2: ......
Page 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Page 325: ...I 323 MEMO ...
Page 329: ......