4 TROUBLESHOOTING
4.5 List of Error Codes
225
4
D2D0H
The station number specified for the
CCPASETX instruction is already in use.
• Execute the instruction again after correcting the station number in the
network configuration setting data to a unique value.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D2D1H
The link device range assignment specified
for each station in the CCPASETX
instruction is incorrect.
• Execute the instruction again after correcting the offset or the number of
points of link devices in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D2D2H
The IP address/port number of the target
station is incorrect.
• Execute again after correcting the port number of the target station in the
setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D2D3H
Send processing of the transient
transmission has failed.
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Execute the instruction again after correcting the target IP address of
transient data.
• If the access destination is a module with a different network number,
correct the routing parameter setting.
D602H
Parameter error
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D605H
Parameter error
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D60BH
Parameter error (device overlap error (LB))
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D60CH
Parameter error (device overlap error (LW))
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset or size of the link
device of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D60DH
Parameter error (each station device range
assignment error (LB))
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the size of the link device of
the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D60EH
Parameter error (each station device range
assignment error (LB))
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset of the link device
of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D60FH
Parameter error (each station device range
assignment error (LW))
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the size of the link device of
the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D610H
Parameter error (each station device range
assignment error (LW))
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the offset of the link device
of the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D611H
Parameter error (each station device range
assignment error (RWw))
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the size of the link device of
the slave station in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Error
code
Error definition and causes
Action
Detailed
information 1
Detailed
information 2