4 TROUBLESHOOTING
4.5 List of Error Codes
213
4
3602H
Inter-module synchronization cycle failure
occurred between networks.
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• Check if the switching hub and the cables are connected properly.
• After taking the above action, power off and on or reset all stations where
the error was detected.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
3603H
The number of the slot on which a module
that cannot be set as the synchronization
master is mounted on is set in "Mounting
Slot No." of the synchronization master in
"System Parameter".
Correct the setting of "Mounting Slot No." of the synchronization master in
"System Parameter".
3604H
A module to operate as an inter-module
synchronous master could not output an
inter-module synchronization signal.
• Check if the switching hub and the cables are connected properly.
• Power off and on or reset the own station.
• When the multiple RJ71GN11-T2s (local station) detects this error, power
off or reset the RJ71GN11-T2s (local station) close to the master station in
connection order.
■
■
Synchronous
master setting
information
• Synchronous
master mounted
slot number
3605H
A module to operate as an inter-module
synchronous master could not output an
inter-module synchronization signal.
• Check the master station condition.
• Check the error of the master station and take action using the module
diagnostics of the engineering tool.
• Check that the settings of the master station are consistent with the one of
the slave station in "Network Configuration Settings" under "Basic
Settings" of the master station.
• Check that the settings of the master station are consistent with the one of
the local station in "IP Address" under "Required Settings" of the local
station.
• Correct the "IP Filter Settings" under "Application Settings".
• Check if the switching hub and the cables are connected properly.
• Power off and on or reset the own station.
• When the multiple RJ71GN11-T2s (local station) detects this error, power
off or reset the RJ71GN11-T2s (local station) in order of connection near
the master station.
■
■
Synchronous
master setting
information
• Synchronous
master mounted
slot number
3607H
The correction value of time counter
calculated by the inter-module
synchronization function exceeds allowable
range successively.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module or base unit. Please consult your local Mitsubishi
representative.
3608H
Inter-module synchronization signals have
not been input for a certain period of time.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module or base unit. Please consult your local Mitsubishi
representative.
3609H
An error has been detected in the inter-
module synchronization function.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module or base unit. Please consult your local Mitsubishi
representative.
360AH
An error has been detected in the inter-
module synchronization function.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module or base unit. Please consult your local Mitsubishi
representative.
360BH
An error has been detected in the inter-
module synchronization function.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module or base unit. Please consult your local Mitsubishi
representative.
360CH
An error has been detected in the inter-
module synchronization function.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of
the module or base unit. Please consult your local Mitsubishi
representative.
Error
code
Error definition and causes
Action
Detailed
information 1
Detailed
information 2