8-3
Refrigerant Control Problems
8-3-1
Units in the Cooling Mode Do Not Operate at Expected Capacity.
1. Phenomena
Although cooling operation starts with the normal remote controller display, the capacity is not enough.
(1) Cause, check method and remedy
Cause
Check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency
does not rise due to high discharge tempera-
ture
Protection works and compressor frequency
does not rise due to high pressure
Pressure drops excessively.
(1)
Check pressure difference between the detected pressure by
the pressure sensor and the actual pressure with self-diagno-
sis LED.
-> If the accurate pressure is not detected, check the pres-
sure sensor.
Refer to the following page(s). [8-5-1 Comparing the High-
Pressure Sensor Measurement and Gauge Pressure]
Note:
Lower inlet pressure by the low pressure sensor than the ac-
tual pressure causes insufficient capacity.
SW4 setting (SW6-10: OFF)
(2)
Check temperature difference between the evaporating tem-
perature (Te) and the target evaporating temperature (Tem)
with self-diagnosis LED.
Note:
Higher Te than Tem causes insufficient capacity.
SW4 setting (SW6-10: OFF)
Note:
Protection works and compressor frequency does not rise
even at higher Te than Tem due to high discharge tempera-
ture and high pressure.
At high discharge temperature:
Refer to the following page(s). [7-3-1 Error Code [1102]]
At high pressure:
Refer to the following page(s). [7-3-3 Error Code [1302]
(during operation)]
2.
HBC LEV1 and 2 actuation failure
Refer to the following page(s). [8-8-2 General Overview on
LEV Operation (HBC)]
Insufficient refrigerant flows due to LEV mal-
function (not enough opening) or protection
works and compressor frequency does not rise
due to pressure drop.
High pressure sensor
Low pressure sensor
SW4
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
SW4
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
Evaporating temperature Te
Target evaporating temperature Tem
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
0000006416.BOOK 10 ページ 2021年10月26日 火曜日 午後5時30分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......