[5-1 Dipswitch Functions and Factory Settings ]
2
-
chapter 5
BS_05_M
5
Cont
rol
1) Unless otherwise specified, leave the switch to OFF where indicated by "-" or where the cells are blank, which may be set to
OFF for a reason.
2) When set to the performance-priority mode, the low-noise mode will be terminated, and the units will operate in the normal
mode.
Cooling: Ambient temperature or the high pressure is high.
Heating: When the outside air temperature is low or when the low pressure is low. Refer to the following page(s). [2-4-7 Var-
ious Control Methods Using the Signal Input/Output Connector on Outdoor Unit]
3) Operation noise is reduced by controlling the compressor frequencies and the rotation speed of the outdoor unit fans.
CN3D needs to be set. Refer to the following page(s). [2-4-7 Various Control Methods Using the Signal Input/Output Connec-
tor on Outdoor Unit]
4) Selectable with the function switches SW6-4 and SW6-5.
5) Keep SW7-1, and -2 set to OFF during normal operation. Leaving these switches to ON will disable the error-detection function
and can lead to equipment damage.
6) Shaded areas (
) indicate factory settings.
SW7
1
Enables or disables the de-
tection of the following
types of inverter compres-
sor errors
ACCT, DCCT sensor er-
ror(5301 Detail code 115,
116)
ACCT, DCCT sensor circuit
error(5301 Detail code 117,
118)
IPM open-phase/CNCT2
connection error(5301 De-
tail code 119)
Wiring connection er-
ror(5301 Detail code 120)
Error detection en-
abled
Error detection dis-
abled (no-load oper-
ation allowed)
Any time after power on
2
Enables or disables no-
load operation of the fan in-
verter
The unit continues no-load
operation for 30 seconds
and comes to an error stop.
See the relevant pages for
details: [8-10-9 Checking
the Fan Board for Damage
at No Load]
No-load operation
disabled
No-load operation
enabled
Any time after power on
3
-
-
-
-
4
-
-
-
-
5
-
-
-
-
6
-
-
-
-
7
-
-
-
-
8
-
-
-
-
9
Switches between the nor-
mal startup mode and the
USB writer rewrite mode
Normal startup
mode
USB writer rewrite
mode
Before power on
10
-
-
-
-
SW6-5
ON
OFF
SW6-4
ON
80 Pa
60 Pa
OFF
30 Pa
0 Pa
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
0000006450.BOOK 2 ページ 2021年10月27日 水曜日 午後12時5分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......