[9-4 Maintenance LED Display and Troubleshooting ]
14
-
chapter 9
BS_09_F
9 USB Func
tion
(5) Maintenance LED displays "Er10."
(Meaning or Cause)
Because there was a problem regarding the control board during data storage, data storage is unfinished.
(Solution)
Perform data storage again.
Remove the USB memory stick from the control board and insert it again. Then conduct data storage using Section [9-2-2
Storing Data on a USB Memory Stick]as a reference.
If this still does not correct the problem, there may be a problem with the control board.
(6) System does not start in Normal Mode.
(Meaning or Cause)
The USB memory stick may be left connected.
(Solution)
Remove the USB memory stick from the control board by referring to <Ending the data storage mode> under Section [9-2-2
Storing Data on a USB Memory Stick]. Then press SWP3 (ENTER). If the problem is not resolved, turn off the power to the
outdoor unit, and restart the unit.
(7) Unit cannot be started in the data storage mode.
(Meaning or Cause)
There may be problems with the control board.
(Solution)
Take the two measures 1 and 2 explained in (2) Storing data on a USB memory stick in 1 Procedure under [9-2-2 Storing Data
on a USB Memory Stick].
If the unit cannot be started up in the data storage mode by following either of the two methods 1 or 2, the control board may
be malfunctioning.
2. Collecting operation data (outdoor unit)
(1) Maintenance LED displays blinking "ON."
(Meaning or Cause)
Despite data collection function being enabled, it is not started yet.
There may be two causes.
Firstly, the initialization process immediately after the system startup may have inhibited the start of data collection.
Secondly, M-NET communication may be underway to enable maintenance tools or collect AE-200 logs.
(Solution)
After a certain time, the problem will resolve itself, requiring no corrective actions.
(2) Maintenance LED displays "F-Er."
(Meaning or Cause)
Because there was a problem with the flash memory used to store operation data, the collection of operation data is unfin-
ished.
(Solution)
Restart the outdoor unit, check the status of data collection.
If the LED displays "F-Er," the flash memory may be broken.
Depending on the local conditions, replace the control board.
When the flash memory is not working correctly, data collection and storage to a memory stick cannot be performed, but the
outdoor unit itself functions normally.
(3) Maintenance LED displays blinking "Err."
(Meaning or Cause)
An error occurred in the unit, suspending data collection.
(Solution)
After resolving the error, resume data collection, referring to 1. Operation procedure (4) Restarting data collection under Sec-
tion [9-2-3 Collecting Operation Data].
0000006418.BOOK 14 ページ 2021年10月13日 水曜日 午前10時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......