[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
BS_07_M
chapter 7 -
43
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-26
Error Code [4250, 4255, 4256] Detail Code 104
1. Error code definition
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
[Outdoor unit]
In the case of 4250
In the case of 4255 and 4256
[HBC]
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance
Problems]
(2)
Inverter output related
Refer to the following page(s).
[8-10-2 Checking the Inverter Board Error Detection Circuit]
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance
Problems]
[8-10-4 Checking the Inverter for Damage at No-Load]
[8-10-5 Checking the Inverter for Damage during Compressor Opera-
tion]
[8-10-15 Checking the Installation Conditions]
(3)
Open phase in the power-supply
due to improper power-supply wir-
ing
Refer to item (6) in section [6-1 Read before Test Run]
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to the following page(s).
[8-10-7 Checking the Fan Motor for Ground Fault and Coil Resistance
Problems]
(2)
Fan board failure
Refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-10-9 Checking the Fan Board for Damage at No Load]
[8-10-10 Checking the Fan Board for Damage with Load]
Cause
Check method and remedy
(1)
Grounding fault of pump motor
Refer to the following page(s).
[8-10-11 Checking the Pump Motor for Ground Fault and Coil Resis-
tance Problems]
(2)
Pump INV board failure
Refer to the following page(s).
[8-10-12 Checking the Error-Detection Circuit on the Pump INV Board
(Without load)]
[8-10-13 Checking the Pump INV Board for Damage (Without load)]
[8-10-14 Checking the Pump INV Board for Damage (During pump op-
eration)]
0000006452.BOOK 43 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......