[2-4 M-NET Address Settings ]
4
-
chapter 2
BS_02_L
2
Rest
rict
io
ns
2-4
M-NET Address Settings
2-4-1
Address Settings List
1. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the setting
range.
*2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50."
*3. To set the ME remote controller address to "200," set the rotary switches to "00."
*4. Some models of indoor units have two or three control boards.
Assign an address to the No.1, No. 2, and No. 3 control boards so that the No. 2 control board address equals the No. 1 control board
address plus 1, and that the No. 3 control board address equals the No. 1 control board address plus 2.
*5. No address settings are required for units in a system with a single outdoor unit (with some exceptions).
Address setting is required if a sub HBC are connected.
Unit or controller
Sym-
bol
Address
setting
range
Setting method
Factory
address
setting
CITY MULTI
indoor unit
Main/sub unit
IC
0, 01 to
50
*1 *4 *5
Assign the smallest address to the main indoor unit in the
group, and assign sequential address numbers to the
rest of the indoor units in the same group.
In a system with two or more HBCs, make the settings for
the indoor units in the following order.
(i) Indoor unit to be connected to the main HBC
(ii) Indoor unit to be connected to the sub HBC 1
(iii) Indoor unit to be connected to the sub HBC 2
(iv) Indoor unit to be connected to the sub HBC 3
Make the settings for the indoor units in the way that the for-
mula "(i) < (ii) < (iii) < (iv)" is true.
00
M-NET
adapter
M-NET con-
trol interface
Free Plan
adapter
LOSSNAY
LC
0, 01 to
50
*1 *4 *5
Assign an arbitrary but unique address to each of these units
after assigning an address to all indoor units.
00
ME remote
controller
Main remote
controller
RC
101 to 150
Add 100 to the smallest address of all the indoor units in the
same group.
101
Sub remote
controller
RC
151 to
200
*3
Add 150 to the smallest address of all the indoor units in the
same group.
MA remote controller
MA
No address settings required. (The main/sub setting must be made if 2 re-
mote controllers are connected to the system.)
Main
CITY MULTI outdoor unit
OC
0, 51 to
100
*1 *2 *5
Assign an address that equals the lowest address of the in-
door units in the same refrigerant circuit plus 50.
00
Auxiliary out-
door unit
HBC (main)
HB
0, 51 to
100
*1 *2 *5
Assign an address that equals the address of the outdoor
unit in the same refrigerant system plus 1.
If a given address overlaps any of the addresses that are
assigned to the outdoor units or to the sub HBC, use a
different, unused address within the setting range.
00
HBC (sub)
HS1
HS2
HS3
51 to 100
*2
Assign an address to both the sub HBC that equals the
lowest address of the indoor units that are connected to
each of them plus 50.
If a sub HBC is connected, the automatic startup function
is not available.
0000006407.BOOK 4 ページ 2021年10月12日 火曜日 午後4時22分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......