[2-1 System Configurations ]
BS_02_L
chapter 2 -
1
2
Rest
rict
io
ns
2 Restrictions
2-1
System Configurations
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
3) Only either P**Y-W model indoor units (equipped with a flow control valve) or P**Y-WP/WL model indoor units (without a flow
control valve) can be connected to the HBC. (Combining different models of indoor units will cause a connection error.)
4) The following models of indoor units can be used as indoor units equipped with a flow control valve when used with the op-
tional valve kit (PAC-SK04VK-E).
<Applicable indoor units>
P**Y-WL**
* The optional valve kit (PAC-SK04VK-E) cannot be installed on P**Y-WP** models.
(2) High COP combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
3) Only either P**Y-W model indoor units (equipped with a flow control valve) or P**Y-WP/WL model indoor units (without a flow
control valve) can be connected to the HBC. (Combining different models of indoor units will cause a connection error.)
4) The following models of indoor units can be used as indoor units equipped with a flow control valve when used with the op-
tional valve kit (PAC-SK04VK-E).
<Applicable indoor units>
P**Y-WL**
* The optional valve kit (PAC-SK04VK-E) cannot be installed on P**Y-WP** models.
Outdoor units
HBC
Number of
connectable
HBC
Sub-HBC
Maximum
number of
connectable
Sub-HBC
Maximum total
capacity of
connectable
indoor units
Maximum
number of
connectable
indoor units
Types of
connectable
indoor units
M200YNW-A1
CMB-
WM350F-AA
1
CMB-
WM108V-BB
CMB-
WM1016V-BB
3
100 - 300
30
W/WP/WL10 -
W/WP/WL125
models
R32 series
indoor units
M250YNW-A1
125 - 375
37
M300YNW-A1
150 - 450
45
M350YNW-A1
175 - 525
50
M400YNW-A1
CMB-
WM500F-AA
1
200 - 600
50
M450YNW-A1
225 - 675
50
M500YNW-A1
250 - 750
50
Outdoor units
HBC
Number of
connectable
HBC
Sub-HBC
Maximum
number of
connectable
Sub-HBC
Maximum total
capacity of
connectable
indoor units
Maximum
number of
connectable
indoor units
Types of
connectable
indoor units
EM200YNW-A1
CMB-
WM350F-AA
1
CMB-
WM108V-BB
CMB-
WM1016V-BB
3
100 - 300
30
W/WP/WL10 -
W/WP/WL125
models
R32 series indoor
units
EM250YNW-A1
125 - 375
37
EM300YNW-A1
150 - 450
45
EM350YNW-A1
175 - 525
50
EM400YNW-A1
CMB-
WM500F-AA
1
200 - 600
50
EM450YNW-A1
225 - 675
50
EM500YNW-A1
250 - 750
50
0000006407.BOOK 1 ページ 2021年10月12日 火曜日 午後4時22分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......