[5-1 Dipswitch Functions and Factory Settings ]
BS_05_M
chapter 5 -
3
5
Cont
rol
7) Selectable with the function switches SW6-9 and SW6-10.
SW6-10
ON
OFF
SW6-9
ON
Self-diagnosis monitor display (round
type LED) No. 0 to 1023
Self-diagnosis monitor display (7seg
LED) No. 1024 to 2047
OFF
SW4 function setting mode No. 0 to 1023
Self-diagnosis monitor display (7seg
LED) No. 0 to 1023
Switch
Function
Function according to switch setting
Switch setting timing
OFF (LED3 Unlit)
ON (LED3 Lit)
SW4
SW6-10:
OFF
1-10
1:ON, 0:OFF
Self-diagnosis/operation
monitor
Refer to the following page(s). [10 LED Sta-
tus Indicators]
Anytime after power on
SW4
1-10
[0:OFF,
1:ON]
(Note 1)
SW6-10:ON
No.769
1000000011
Test run mode: ON/OFF
Stops all ICs
Sends a test-run sig-
nal to all IC
Anytime after power on
No.817
1000110011
Starts up drive recorder
Enabled
Disabled
Anytime after power on
No.818
0100110011
Data collection during an
error
Disabled
Enabled
Anytime after power on
No.832
0000001011
Cumulative compressor
operation time deletion
Retained
Cleared
Anytime after power on (OFF
→
ON)
No.848
0000101011
Continuous heating cycle
function
Disabled
Enabled
After being energized and while the compres-
sor is stopped
No.876
0011011011
High-pressure over-rise
backup setting
SV2 is used.
LEV9 is used.
After being energized and while the compres-
sor is stopped
No.885
1010111011
Fan speed setting at low
outside temperature heat-
ing
Refer to Note 8).
After being energized and while the compres-
sor is stopped
No.886
0110111011
After being energized and while the compres-
sor is stopped
No.891
1101111011
Smooth auto-shift startup
mode
Disabled
Enabled
After being energized and while the compres-
sor is stopped
No.896
0000000111
Clearance of error
history SW
OC
Retained (IC/OC)
Deleted (IC/OC)
Anytime after power on (OFF
→
ON)
No.897
1000000111
High sensible heat opera-
tion setting
Depends on the combined setting with No.
900 (Note 7)
Anytime after power on (OFF
→
ON)
No.900
0010000111
High sensible heat opera-
tion setting
Depends on the combined setting with No.
897 (Note 7)
Anytime after power on (OFF
→
ON)
No.912
0000100111
Pump down function
Normal control
Pump down opera-
tion
After being energized and while the compres-
sor is stopped
No.913
1000100111
Forced defrost (Note 2)
Normal control
Forced defrost starts
10 minutes after the completion of defrost op-
eration (OFF
→
ON) or 10 minutes after com-
pressor start-up (OFF
→
ON)
No.915
1100100111
Defrost start temperature
(Note 2)
(E)P200, (E)P250:
-10°C [14°F]
(E)P300 - (E)P500:
-8°C [18°F]
-5°C [23°F]
Anytime after power on
No.916
0010100111
Defrost end temperature
(Note 2)
7°C [45°F]
12°C [54°F]
Anytime after power on
No.918
0110100111
Changes the defrost timer
setting (Note 2)
50 minutes
90 minutes
Anytime after power on (OFF
→
ON)
No.921
1001100111
Temperature unit display
°C
°F
Anytime after power on
No.922
0101100111
Refrigerant amount adjust-
ment
Normal control
Refrigerant amount
adjust mode
Anytime after power on (except during initial
startup/becomes ineffective 90 minutes after
compressor started up.)
No.933
1010010111
Snow sensor setting
Effective only when
TH7
≤
5 is true or the
snow sensor contact
input is on.
Effective when TH7
≤
5 is true
Anytime after power on
No.934
0110010111
Snow sensor setting
Continuous fan op-
eration (FAN=50%)
Intermittent fan op-
eration (100% for 5
minutes
↔
0% for 30
minutes)
Anytime after power on
No.935
1110010111
High heating power (at low
outside temperature)
Effective
Ineffective
Anytime after power on
No.956
0111011110
SV2 control time setting af-
ter recovery from defrost
Always ON
5 minutes
After being energized and while the compres-
sor is stopped
No.958
0111110111
Clear the history of com-
pleting initial control
Retained
Cleared
After being energized and while the compres-
sor is stopped
* Effective only OFF to ON
No.982
0110101111
Target evaporation tem-
perature setting
Refer to Note 3).
Anytime after power on
No.997
1010011111
Multiple-stage low-noise
setting
Depends on the combined setting with No.
1006 (Note 6)
Depends on the combined setting with 997
(Note 7)
After being energized and while the compres-
sor is stopped
No.1006
0111011111
After being energized and while the compres-
sor is stopped
0000006450.BOOK 3 ページ 2021年10月26日 火曜日 午後7時2分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......