[8-13 Parts Replacement Instructions (Outdoor Unit) ]
BS_08_L
chapter 8 -
97
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
After replacing the compressor, set SW4 (832) and (958) to “ON” before conducting a test run.
After the test run has completed, set SW4 (832) and (958) to “OFF.”
Figure 9
(12) Remove the four bolts holding the compressor down. (See Figure 12.)
The two bolts in the front are also holding down the metal sheets.
(13) Tilting the compressor will cause the refrigerant oil to leak. Seal the pipe where it was cut or removed at the brazed
section.
(14) After replacing the compressor, braze the pipes that were removed as they were.
In case of brazing the suction pipe, protect the surrounding components such as the control box, ACC, compressor cover,
and damper with a fire protection panel (e.g., recommended felt soaked in water), attach the supplied pipe,and perform
brazing. (See Figure 13.)
*Perform brazing, referring to "Notes on replacing refrigerant circuit parts (check valve block assemblies, four-way valves,
solenoid valves, and LEVs)" in 8-13-4.
(15) The recommended tightening torque for the compressor fixing bolts is 3.0 N·m. Fasten the bolts using a torque wrench or
other tool that can apply the specified torque.
(16) Re-place the compressor covers in the reverse order as they were removed.
*Hold the TH15 wiring in place with the bands to keep the wiring from coming in contact with insulation 2. (See Figures 3
and 7.)
Figure 12
Control box
Attach the supplied pipe.
ACC
Compressor
Fire protection panel
(Recommended felt soaked in water etc.)
Figure 13
Damper
Area to be brazed
Compressor fixing bolts
Compressor fixing
metal sheets and bolts
(9) Remove the pipe cover and the damper, and cut the suction pipe where indicated in Figure 9.
(10) Remove the pipe covers, and then remove the braze. (See Figure 10.)
* Do not force the injection pipe to deform.
(11) Remove the compressor discharge pipe by cutting the pipe where indicated in Figure 11 or by removing the braze.
Figure 11
Damper and cable tie
(Length: 180 mm and 250 mm)
Pipe cover
(ID: 43 mm; Length: 260 mm)
Cut the suction
pipe here.
Cut the compressor
discharge pipe here.
Figure 10
Remove the braze here.
Remove the two
pipe covers.
* Save the pipe
covers for later
use.
0000006416.BOOK 97 ページ 2021年10月26日 火曜日 午後5時30分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......