[5-2 Outdoor Unit Control ]
12
-
chapter 5
BS_05_M
5
Cont
rol
5-2-4
Refrigerant Bypass Control
Bypass solenoid valves, which bypass the high- and low- pressure sides, perform the following functions.
(1) Bypass solenoid valve (SV1a) (ON = Open)
(2) Bypass solenoid valve (SV2) (ON = Open)
(3) Bypass LEV (LEV9)
Operation
SV1a
ON OFF
When starting-up the compressor of each
outdoor unit
ON for 4 minutes.
After the restoration of thermo or 3 minutes
after restart
ON for 4 minutes.
During cooling or heating operation with the
compressor stopped
Always ON.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
After the operation has stopped
ON for 3 minutes.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
During defrost operation
ON
While the compressor is operating at the
minimum frequency and when the low pres-
sure (63LS) drops (3 or more minutes after
compressor startup)
When the low pressure (63LS)
drops below 0.23 Mpa [33 psi]
during cooling-only or cooling-main
operation.
When the low pressure (63LS)
drops below 0.38 Mpa [55 psi]
during cooling-only or cooling-main
operation.
When high pressure (63HS1) rises
When 63HS1 exceeds
3.62MPa[525psi]
When 63HS1 is 3.43MPa [497 psi]
or below in 30 seconds
Operation
SV2
ON
OFF
When high pressure (63HS1) rises during
heating operation
While the compressor is operating
at the minimum frequency and
when 63HS1 exceeds 3.43 MPa
[497 psi] during heating-only or
heating-main operation
When 63HS is 2.65 MPa [384 psi]
or below
When low pressure (63LS) drops during
heating operation
When 63HS is below 1.47 MPa
[213 psi] and 63LS is below 0.25
MPa [36 psi]
When 63HS is above 1.72 MPa
[249 psi] or 63LS is above 0.39
MPa [56 psi]
When the defrost operation is completed
SW4(956)=OFF Always ON
SW4(956)=ON ON for 5 minutes
Others
Always OFF (Closed)
Operation
LEV9
480 pulses
Normal control
When high pressure (63HS1) rises during
heating operation
SW(876) = ON
While the compressor is operating
at the minimum frequency and
when 63HS1 exceeds 3.43 MPa
[497 psi] during heating-only or
heating-main operation
When 63HS is 2.65 MPa [384 psi]
or below
0000006450.BOOK 12 ページ 2021年10月26日 火曜日 午後7時2分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......