7-5-2
Error Code [3511]
1. Error code definition
Refrigerant overcooling
2. Error definition and error detection method
1) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met (for the first time) during oper-
ation, the outdoor unit will stop, go into the three-minute restart delay mode, and then automatically resume operation after
three minutes have passed.
2) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met again (for the second time)
within 30 minutes of the first stoppage of the outdoor unit explained above, the outdoor unit will stop, go into the three-minute
restart delay mode, and then automatically resume operation after three minutes have passed.
3) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met again (for the third time) within
30 minutes of the second stoppage of the outdoor unit explained above and before the condition "THHS > A
*1
°C remains true
for continuous 2 minutes" has been met, the unit will come to an abnormal stop, and this error will be indicated as "3511."
4) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met (regardless of the first or second
time) after 30 minutes of the first occurrence or after the condition "THHS > A
*1
°C remains true for continuous 2 minutes" has
been met, it is considered as the first occurrence, and the unit will follow the same behavior as the one described in item 1)
above.
5) For 30 minutes after the stoppage of the outdoor unit, or the period up to the time when the condition "THHS > A
*1
°C remains
true for continuous 2 minutes" has been met is considered as a preliminary error, and this state will be indicated on the LED.
*1 During cooling: A = Outside temperature TH7; During heating: A = Evaporation temperature Te
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Outdoor unit LEV9 malfunction
Check the operation of unit in the Cooing or in the Heating
mode.
LEV9
Refer to [8-8 Troubleshooting LEV, FCV Problems].
(2)
THHS failure
1)
Check the IGBT on the INV board for proper mounting.
2)
Check the THHS sensor reading on the LED.
→
Replace the INV board if the THHS value is abnormal.
(3)
Thermistor failure (TH7)
Resistance value of the thermistor
(4)
Low-pressure sensor fault
Refer to [8-5 Pressure Sensor Circuit Configuration and
Troubleshooting Pressure Sensor Problems]
0000006452.BOOK 25 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......