[5-3 HBC Control ]
BS_05_M
chapter 5 -
31
5
Cont
rol
5-3-8
Refrigerant Recovery Control
The refrigerant recovery control function controls the refrigerant flow at the HBC during heating operation to keep the refrig-
erant from collecting inside the HBC.
It is also performed during cooling operation to prevent an excessive amount of refrigerant from accumulating in the outdoor
heat exchanger.
Starting criteria for the refrigerant recovery cycle (during Cooling-only, Cooling-main, Heating-only, or Heating-main
mode)
The refrigerant recovery mode starts when all of the following conditions are met:
1) When 5 minutes have passed in the Heating-only or Heating-main mode or 30 seconds have passed in the Cooling-only or
Cooling-main mode since the completion of the previous refrigerant recovery cycle AND the when following conditions are
met.
Outdoor unit TH4 > 105°C [221°F]
2) When the port is not in the 4-minute restart delay mode
Starting criteria for the refrigerant recovery cycle (during Cooling-only, Cooling-main, Heating-only, or Heating-main
mode)
The opening of LEV1 and LEV2 on the HBC is increased.
5-3-9
Backup Control
The following backup control is started on the HBC as necessary.
(1) Backup mode for plate heat exchanger protection
The following control is performed depending on the outlet pipe temperature of the plate heat exchanger for freeze-up pro-
tection.
[Cooling-main/Heating-main operation]
1) Outdoor unit
Cooling-main operation: Continued; Heating-main operation: Continued
2) HBC
(2) Heating water temperature backup mode
When the heating operation can be continued without receiving heat from the refrigerant due to water temperature rise during
heating operation (the outlet pipe temperature of the plate heat exchanger is 70ºC or above), the outdoor unit goes into the
Thermo-OFF mode, and the heating operation is performed only by circulating the hot water by the water pump. When the
water temperature decreases to a certain level (the outlet temperature of the plate heat exchanger is 45ºC or below), the out-
door unit starts up.
Control mode
Cooling-main/Heating-main
Cooling-only
Outdoor unit
Operation
mode
Continues the current operation
Cooling-only Thermo-OFF
HBC
21S4Ma
Heating side: open (de-energized)
Cooling side: open (energized)
21S4Mb
Cooling side: open (de-energized)
Cooling side: open (de-energized)
LEV1
Maintains the opening that was used in the
previous operation mode
Opening during Cooling-only Thermo-OFF
LEV2
41 pulses: fully closed
Opening during Cooling-only Thermo-OFF
LEV3
3000 pulses: fully open
Opening during Cooling-only Thermo-OFF
SV1
Closed
Open
PUMP1
Continues the heating operation
Continues the cooling-only operation
PUMP2
Continues the cooling operation
Continues the cooling-only operation
VB3a~p
The opening depending on the indoor unit
operation mode
The opening depending on the indoor unit
operation mode
0000006450.BOOK 31 ページ 2021年10月26日 火曜日 午後7時2分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......