[3-3 Functions of the Major Components of Outdoor Unit ]
BS_03_L
chapter 3 -
15
3 Major Compon
ent
s
, Their Fun
ct
io
ns
a
n
d
Re
frig
e
ra
n
t
Circ
ui
ts
Thermis-
tor
TH3
(Pipe
temperature)
Controls defrosting during heating
operation
Degrees Celsius
0°C[32°F] :15 k
Ω
10°C[50°F] :9.7 k
Ω
20°C[68°F] :6.4 k
Ω
25°C[77°F] :5.3 k
Ω
30°C[86°F] :4.3 k
Ω
40°C[104°F] :3.1 k
Ω
Resistance check
TH7
(Outdoor tem-
perature)
1) Detects outdoor air tempera-
ture
2) Controls fan operation
TH5
(Pipe tempera-
ture)
Fan operated on the 63LS and
TH5 values.
TH15
(Compressor
shell bottom
temperature)
Detects compressor shell bottom
temperature
THHS
Inverter
heat sink tem-
perature
Inverter overheating protection
Degrees Celsius
0°C[32°F] :161 k
Ω
10°C[50°F] :97 k
Ω
20°C[68°F] :60 k
Ω
25°C[77°F] :48 k
Ω
30°C[86°F] :39 k
Ω
40°C[104°F] :25 k
Ω
Sole-
noid
valve
SV1a
Discharge-suc-
tion
bypass
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
Continuity check
with a tester
SV2
Prevention of low-pressure drop
Refrigerant equalization control
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
LEV
LEV2a, 2b, 2c
LEV2c is
only on the
(E)M500
models.
(During cooling)
Heat exchanger capacity control
(During heating)
Refrigerant equalization control
DC12V
Opening of stepping motor
driving valve 0-3000 pulses
(LEV2a, 2b)
0-3000 pulses
(LEV2d, (E)M200-300)
0-6000 pulses
(LEV2d, (E)M350-500)
Continuity Test
with a Tester.
Continuity be-
tween white and
orange.Continui-
ty between yel-
low, brown, and
blue
LEV2d
Heat exchanger capacity control
LEV4
Injection amount control
DC12V
Opening of stepping motor
driving valve 0-480 pulses
(direct driven type)
LEV9
Refrigerant cooling control
4-way
valve
21S4a, b
Changeover between heating and
cooling
AC220 - 240V
Dead: cooling cycle
Live: heating cycle
Continuity check
with a tester
21S4c
(E)M500
models
only
Fan mo-
tor
FAN motor 1, 2 FAN motor
2 is only on
the
(E)M350 -
(E)M500
models.
Regulates the heat exchanger ca-
pacity by adjusting the operating
frequency and operating the pro-
peller fan based on the operating
pressure.
(E)M200 - (E)M300,
(E)M500
AC380 - 460V, 920W
(E)M350 - (E)M450
AC380 - 460V, 460W
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
R = 15k
0
R = 3460
R = 15
0/80
t
3460 273 t
1
273
1
exp
R = 17k
50
R = 4016
R = 17
25/120
t
4016
273 t
1
323
1
exp
Yellow
White
Orange
Brown Blue
M
0000006412.BOOK 15 ページ 2021年10月12日 火曜日 午後4時33分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......