[2-7 Example System with an MA Remote Controller ]
BS_02_L
12
-
chapter 2
2
Rest
rict
io
ns
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
unit (OC), of the terminal block for indoor-outdoor trans-
mission line (TB3) on the main HBC (HB), and of the ter-
minal block for indoor-outdoor transmission line (TB5) on
each indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor unit
(OC), the S terminal of the terminal block (TB3) on the
HBC (HB), and the S terminal of the terminal block (TB5)
on the indoor unit (IC) with the shield of the shielded ca-
ble.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Connect terminals 1 and 2 on the terminal block for MA
remote controller line (TB15) on the indoor unit (IC) to the
terminal block on the MA remote controller (MA).
(Non-polarized two-wire)
When 2 remote controllers are connected to the sys-
tem
When 2 remote controllers are connected to the system,
connect terminals 1 and 2 of the terminal block (TB15) on
the indoor unit (IC) to the terminal block on the two MA
remote controllers.
Set one of the MA remote controllers as a sub controller.
(Refer to the Instruction Manual for the MA remote con-
troller for the setting method.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisy-
chain terminals 1 and 2 on the terminal block (TB15) on
all indoor units (IC) in the same group, and then connect
terminals 1 and 2 on the terminal block (TB15) on the in-
door unit on one end to the terminal block on the MA re-
mote controller. (Non-polarized two-wire)
When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor ad-
dress setup" is not available.
4) Switch setting
No address settings required.
5) When replacing the control board on only some of the
outdoor units, delete all connection information. (Refer to
[5-1-1 Outdoor Unit Switch Functions and Factory Set-
tings] for information on switch functions.)
(5) Address setting method
Proce-
dures
Unit or controller
Address set-
ting range
Setting method
Notes
Factory
setting
1
Indoor unit
Main unit
IC
No settings
required.
-
Port number setting is re-
quired
For information about how to
perform a group operation of
indoor units that feature dif-
ferent functions, refer to the
following page(s). [2-7-2
Single Refrigerant System]
00
Sub unit
IC
2
MA
remote con-
troller
Main
remote con-
troller
MA
No settings
required.
-
Main
Sub
remote con-
troller
MA
Sub
remote con-
troller
Settings to be
made with the
Sub/Main
switch
3
Outdoor unit
OC
No settings
required.
-
00
4
Auxiliary
outdoor unit
HBC
HB
No settings
required.
-
00
0000006407.BOOK 12 ページ 2021年10月12日 火曜日 午後4時22分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......