[2-7 Example System with an MA Remote Controller ]
BS_02_L
chapter 2 -
19
2
Rest
rict
io
ns
2-7-5
System with a Connection of System Controller to Indoor-Outdoor
Transmission Line
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group
of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for transmis-
sion line for centralized control (TB7) on only one of the outdoor
units.
6) A maximum of three system controllers can be connected to the in-
door-outdoor transmission line. (AE-200, AG-150A, GB-50ADA, or
G(B)-50A are not connectable.)
7) When the total number of indoor units exceeds 20 (12 if one or more
indoor units of the 200 model or above is connected), it may not be
possible to connect a system controller to the indoor-outdoor trans-
mission line.
8) When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
The left table shows the number of transmission boosters that is re-
quired by the system with four HBCs. For each HBC added or sub-
tracted, subtract or add two indoor units.
Refer to the DATABOOK for further information about how many
booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
[AWG16] or larger)
L12
200m [656ft]
L22
200m [656ft]
L25
200m [656ft]
The maximum piping length between OC and HB is 150 m.
2) Transmission line for centralized control
L31
200m [656ft]
3) MA remote controller wiring
Same as 2-7-1
4) Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L25+L31+L12
1000 m [3280ft] (500 m [1640ft])
*1
L12+L31+L22
1000 m [3280ft] (500 m [1640ft])
*1
*1 If a given system includes one or more unit or remote controller
that does not support the maximum allowable cable distance of
1000 m [3280 ft], the maximum allowable cable distance in the
system will be 500 m [1640 ft]. Refer to the latest catalog for in-
formation on which units and remote controllers support the max-
imum allowable cable distance of 1000 m [3280 ft].
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
A
1
B
2
MA
A
1
B
2
MA
LC
TB5
S
07
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
05
04
LC
TB5
S
08
IC
TB5
S
TB15
1 2
03
A
1
B
2
MA
IC
TB5
S
TB15
1 2
06
A
1
B
2
MA
A
1
B
2
MA
Group
Group
Group
Group
Group
m3
Interlock operation with
the ventilation unit
OC
Connect
m2
m1
Note1 LM adapters cannot be connected to the
indoor-outdoor transmission line.
TB3
TB7
S
51
OC
TB3
TB7
S
54
L31
A B S
L25
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
M2
M1
Not
Connect
CN41 CN40 Replace
SW5-1 OFF ON
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
System controller
Note1
S
HB
TB3
52
S
HB
TB3
55
L22
L12
Number of transmission boost-
er (sold separately) required
1 unit
2 units
When the W/WP/WL200 and
W/WP/WL250 models are not included in
the connected indoor units
25 - 50 units
-
When the W/WP/WL200 and
W/WP/WL250 models are included in the
connected indoor units
19 - 37 units 38 - 50 units
0000006407.BOOK 19 ページ 2021年10月12日 火曜日 午後4時22分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......