[8-3 Refrigerant Control Problems ]
BS_08_L
chapter 8 -
11
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
Cause
Check method and remedy
3.
RPM error of the outdoor unit FAN
Refer to the following page(s).
[8-7 Troubleshooting Outdoor Unit Fan Problems]
[7-3-3 Error Code [1302] (during operation)]
Motor failure or board failure, or airflow rate de-
crease due to clogging of the heat exchanger
The fan is not properly controlled as the outdoor
temperature cannot be precisely detected by the
temperature sensor.
The fan is not properly controlled as the pres-
sure cannot be precisely detected by the pres-
sure sensor.
4.
Long piping length
The cooling capacity varies greatly depending on
the pressure loss. (When the pressure loss is
large, the cooling capacity drops.)
Check the piping length to determine if it is contributing to
performance loss.
Piping pressure loss can be estimated from the temperature
difference between the indoor unit heat exchanger outlet
temperature and the saturation temperature (Te) of 63LS.
->Correct the piping.
5.
Piping size is not proper (thin)
6.
Insufficient refrigerant amount
Protection works and compressor frequency does
not rise due to high discharge temperature.
Refer to item 1 (Compressor frequency does not rise suffi-
ciently.) on the previous page.
Refer to the following page(s). [6-3 Evaluating and Adjusting
Refrigerant Charge]
7.
Clogging by foreign object
Check the temperature difference between in front of and
behind the place where the foreign object is clogging the
pipe (upstream side and downstream side). When the tem-
perature drops significantly, the foreign object may clog the
pipe.
-> Remove the foreign object inside the pipe.
8.
The indoor unit inlet temperature is excessively
low. (Less than 15°C [59°F] WB)
Check the inlet air temperature and for short cycling.
Change the environment where the indoor unit is used.
9.
Compressor failure
The amount of circulating refrigerant decreases
due to refrigerant leak in the compressor.
Check the discharge temperature to determine if the refrig-
erant leaks, as it rises if there is a leak.
10.
HBC LEV3 actuation failure
Sufficient cold water is not supplied as sufficient
sub cool cannot be secured on the HBC due to
LEV1, 2, and 3 actuation failure.
Refer to the following page(s). [8-8-2 General Overview on
LEV Operation (HBC)]
11.
TH12, TH15 and 63HS1 sensor failure or faulty
wiring
LEV3 is not controlled normally.
Check the thermistor.
Check wiring.
12.
HBC valve block actuation failure Sufficient cold
water is not supplied because of the insufficient
water flow rate and coexistence of cold and hot
water on the HBC due to valve block actuation fail-
ure.
Refer to the following page(s). [8-14 HBC Maintenance In-
structions (Applicable to main and sub HBCs)]
13
Open phase in the power-supply due to improper
power-supply wiring
Make sure that the power-supply wiring is properly connect-
ed. (Refer to item (6) in section [6-1 Read before Test Run].)
Possible open phase.
14
LEV4 failure
Refer to the following page(s). [8-8-3 Possible Problems and
Solutions]
0000006416.BOOK 11 ページ 2021年10月26日 火曜日 午後5時30分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......