12. Installation restrictions for outdoor units
Do not install the unit where combustible gas may leak.
- If combustible gas accumulates around the unit, fire or explosion may result.
•
Provide sufficient space around the unit for effective operation, efficient air movement, and ease of access for
maintenance.
•
Note that refrigerant gas is heavier than air and will therefore tend to collect in low spots such as basements.
•
When an indoor unit that draws in outside air exits near the outdoor unit, be careful not to affect the normal
operation of the indoor unit.
•
When the amount of drain water is excessive, drain water comes out of the outdoor unit along the panel during
heating operation. Provide sufficient space around the unit.
•
R32 is heavier than air—as well as other refrigerants—so tends to accumulate at the base (in the vicinity of the
floor). If R32 accumulates around the base, it may reach a flammable concentration in case the room is small. To
avoid ignition, maintain a safe work environment by ensuring appropriate ventilation. If the refrigerant leaks in a
room or an area that has insufficient ventilation, refrain from using flames until the work environment is improved by
ensuring appropriate ventilation.
•
Do not install the outdoor unit in a basement or machinery room, where the refrigerant stagnates.
•
Install the outdoor unit in a place where at least one of the four sides is open.
•
If the unit needs to be installed in a space where all four sides are blocked, confirm that one of these situations (A,
B, or C) is satisfied.
A: Secure sufficient installation space (minimum installation area: Amin).
Install the unit in a space with an installation area of Amin or more, corresponding to the refrigerant amount
(M). (M = factory-charged refri refrigerant to be added on site)
M (kg)
Amin (m
2
)
Amin
10
112
20
223
30
334
40
445
50
556
60
667
B: Install the unit in a space with a wall height of ≤ 0.125 m.
Good
Good
Good
NG
Wall height ≤ 0.125 m
(No restrictions apply to
the refrigerant amount)
Wall height ≤ 0.125 m
0000006448.BOOK 11 ページ 2021年10月6日 水曜日 午後1時57分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......