[5-2 Outdoor Unit Control ]
18
-
chapter 5
BS_05_M
5
Cont
rol
5-2-8
Outdoor Unit Fan Control
(1) Control method
Depending on the capacity required, the rotation speed of the outdoor fan is controlled by the inverter to keep a constant con-
densing temperature (outside tempe 10°C [50°F]) during cooling operation and a constant evaporation temperature
(0°C [32°F] = 0.71 MPa [103 psi]) during heating operation.
(2) Control
Outdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor).
The fan operates at full speed for 5 seconds after start-up.(Only when TH7<0°C [32°F])
The outdoor unit fan stops during defrost operation.
Both fans operate on the (E)M350, (E)M400, (E)M450, and (E)M500 models of outdoor units.
(3) Outdoor heat exchanger capacity control pattern
Outdoor fan rotation control is supported.
As the operation pattern number increases, the refrigerant bypassing the outdoor heat exchanger increases. As the operation
pattern number increases, the capacity difference becomes smaller between cooling operation and heating operation.
In each mode, the four-way valve and the expansion valve operate as shown in the table below. The expansion valve may
open or close during the refrigerant equalization control or the evaporation temperature control. See [5-2-9 Expansion valve
control (LEV2a, LEV2b, LEV2c, and LEV2d)]
(4) Evaporation temperature control (Expansion valves LEV2a, LEV2b, LEV2c, and LEV2d)
LEV is controlled every 30 seconds so that the minimum temperature of the liquid refrigerant (TH12) of the Cooling-main heat
exchanger and of the bypass inlet (TH15) of the HBC are in a constant range during Heating-only or Heating-main operation.
Model
Operation
mode
Operation
patterns
Four-way valve
LEV
21S4a
21S4b
21S4c
LEV2a
LEV2b
LEV2c
LEV2d
LEV4
(E)M200,
(E)M250,
(E)M300
models
Cooling-only
Cooling-main
1
OFF
OFF
-
3000
3000
-
41
*Injection
controlled
2
OFF
ON
-
3000
41
-
1000
3
OFF
ON
-
500
41
-
3000
4
OFF
ON
-
300
41
-
3000
Heating-only
1
ON
ON
-
3000
3000
-
41
Heating-main
1
ON
ON
-
3000
3000
-
41
2
ON
ON
-
3000
3000
-
1250
Defrost
1
OFF
OFF
-
3000
3000
-
41
(E)M350,
(E)M400,
(E)M450
models
Cooling-only
Cooling-main
1
OFF
OFF
-
3000
3000
-
20
2
OFF
ON
-
3000
41
-
800
3
OFF
ON
-
3000
41
-
6000
4
OFF
ON
-
1000
41
-
6000
Heating-only
1
ON
ON
-
3000
3000
-
20
Heating-main
1
ON
ON
-
3000
3000
-
20
2
ON
ON
-
3000
3000
-
1000
Defrost
1
OFF
OFF
-
3000
3000
-
20
(E)M500
models
Cooling-only
Cooling-main
1
OFF
OFF
OFF
3000
3000
3000
20
2
OFF
ON
ON
3000
41
41
800
3
OFF
ON
ON
3000
41
41
6000
4
OFF
ON
ON
1000
41
41
6000
Heating-only
1
ON
ON
ON
3000
3000
3000
20
Heating-main
1
ON
ON
ON
3000
3000
3000
20
2
ON
ON
ON
3000
3000
3000
1000
Defrost
1
OFF
OFF
OFF
3000
3000
3000
20
0000006450.BOOK 18 ページ 2021年10月26日 火曜日 午後7時2分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......