[2-7 Example System with an MA Remote Controller ]
BS_02_L
chapter 2 -
13
2
Rest
rict
io
ns
2-7-2
Single Refrigerant System
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a
group of indoor units.
3) When the number of the connected indoor units is as shown in
the table below, one or more transmission boosters (sold sepa-
rately) are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that
are listed in the specifications for each outdoor unit.)
The table above shows the number of transmission boost-
ers that is required by the system with four HBCs. For each
HBC added or subtracted, subtract or add two indoor units.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-1
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as 2-7-1
L2
HB
52
OC
51
TB7
S
TB3
TB3
S
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
A1 B2
MA
A1 B2
MA
LC
TB5
S
05
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
04
03
LC
TB5
S
06
A1 B2
MA
* If the HB address overlaps any of the addresses that are assigned to either the OC or HS, use a different, unused address.
OC and HB addresses (lowest indoor unit address in the group plus +50) have higher priority than the HS address.
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
08
07
A1 B2
MA
A1 B2
MA
M1M2
M1M2
L11
L3
L4
L12
L13
M1 M2
M1 M2
M1 M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1 M2
TB3
S
57
HS
L1
Group
Group
Group
Interlock operation with the ventilation unit
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
m1
m2
m3
Number of transmission booster
(sold separately) required
1 unit
2 units
When the W/WP/WL200 and
W/WP/WL250 models are not includ-
ed in the connected indoor units
25 - 50 units
-
When the W/WP/WL200 and
W/WP/WL250 models are included in
the connected indoor units
19 - 37 units
38 - 50 units
0000006407.BOOK 13 ページ 2021年10月12日 火曜日 午後4時22分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......