[2-9 Example System with an MA and an ME Remote Controller ]
BS_02_L
26
-
chapter 2
2
Rest
rict
io
ns
2-9
Example System with an MA and an ME Remote Controller
2-9-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
(2) Cautions
1) Be sure to connect a system controller.
2) ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote controller ad-
dresses that are smaller than those of the indoor units that are con-
nected to the ME remote controller.
4) No more than 2 ME remote controllers can be connected to a group
of indoor units.
5) No more than 2 MA remote controllers can be connected to a group
of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
7) Replace the power jumper connector of the control board from CN41
to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on the terminal
block for centralized control on only one of the outdoor units.
9) When the number of the connected indoor units is as shown in the
right table, one or more transmission boosters (sold separately) are
required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
The above table shows the number of transmission
boosters that is required by the system with four HBCs.
For each HBC added or subtracted, subtract or add two
indoor units.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
10) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
IC
TB5
S
TB15
1 2
06
106
IC
TB5
S
TB15
1 2
05
A1 B2
MA
A1 B2
RC
A1 B2
MA
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
04
03
104
A1 B2
RC
OC
TB3
TB7
S
51
OC
TB3
TB7
S
53
L31
A B S
L32
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
To be left
unconnected
To be connected
System controller
Note1
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
*2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1 M2
M1 M2
M1 M2
S
HB
TB3
52
S
HB
TB3
54
L22
L12
SW5-1 OFF ON
Move the male connector
from CN41 to CN40.
Group
Group
Group
Group
M1M2
Number of transmission booster
(sold separately) required
1 unit
2 units
3 units
When the W/WP/WL200 and
W/WP/WL250 models are not includ-
ed in the connected indoor units
13 - 32
units
33 - 50
units
-
When the W/WP/WL200 and
W/WP/WL250 models are included in
the connected indoor units
9 - 24
units
25 - 40
units
41 - 50
units
0000006407.BOOK 26 ページ 2021年10月12日 火曜日 午後4時22分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......