[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
BS_07_M
chapter 7 -
13
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-3-3
Error Code [1302] (during operation)
1. Error code definition
High pressure fault 1 (Outdoor unit)
2. Error definition and error detection method
1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the outdoor stops once,
turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor again (the second detection) within 30 minutes after the first
stop of the outdoor unit, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
3) If the pressure of 3.87MPa [561psi] or higher is detected by the pressure sensor (the 15th detection) within 30 minutes of the 14th stop of the
outdoor unit, the outdoor unit will make an error stop, and the error code "1302" will be displayed.
4) If the pressure of 3.78MPa [548psi] or higher is detected more than 30 minutes after the stop of the outdoor unit, the detection is regarded
as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
6) The outdoor unit makes an error stop immediately when not only the pressure sensor but also the pressure switch detects 4.15
+0,-0.15
MPa
[601
+0,-22
psi]
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
HBC LEV malfunction
Heating only or heating main: LEV1, 2, and 3
Defrost: LEV1, 2, and 3
Perform a heating operation and check the operation.
Cooling: Four-way valves
(21S4a, 21S4b, and 21S4c) on the outdoor unit
Expansion valves (LEV2a, 2b, 2c, and 2d)
HBC SV1, 21S4Ma, and 21S4Mb
Heating: HBC SV1, 21S4Ma, and 21S4Mb
Refer to the following page(s). [8-8 Troubleshooting LEV,
FCV Problems]
(2)
HBC SV1, 21S4Ma, and 21S4Mb malfunction
→
Cooling only or defrost
(3)
HBC SV1, 21S4Ma, and 21S4Mb malfunction
→
Cooling only or cooling main
(4)
HBC SV1, 21S4Ma, and 21S4Mb malfunction
→
Heating only or heat-
ing main
HBC SV1, 21S4Ma, and 21S4Mb malfunction
→
Cooling only or cool-
ing main
(5)
Actuation failure in the four-way valve (21S4a, 21S4b or 21S4c) or the
expansion valve (LEV2a, LEV2b, LEV2c, or LEV2d)
→
Cooling-only or
cooling-main
(6)
Port address setting error.
Confirm the port address of the indoor unit.
(7)
Refrigerant service valve actuation failure
Confirm that the refrigerant service valve is fully open.
(8)
Short cycle on the outdoor unit
Check the outdoor units for problems and correct them, if
any.
(9)
Dirty heat exchanger of the outdoor unit
(10)
Outdoor fan (including fan parts) failure, motor failure, or fan controller
malfunction
Items (8) through (10) above reduce the condensing capability of the
unit, resulting in high-pressure rise during cooling operation.
Check the fan on the outdoor unit.
Refer to the following page(s). [8-7 Troubleshooting Out-
door Unit Fan Problems]
(11)
Solenoid valve (SV1a) malfunction
The by-pass valve (SV1a) can not control rise in high pressure.
Refer to the following page(s). [8-6 Troubleshooting Sole-
noid Valve Problems]
(12)
Thermistor failure (TH3, TH7)
Refer to the following page(s). [7-7-3 Error Code
[5103,5104,5105,5107,5115]]
(13)
Pressure sensor failure
Refer to the following page(s). [8-5-1 Comparing the High-
Pressure Sensor Measurement and Gauge Pressure]
(14)
Failure of the thermistor input circuit and pressure sensor input circuit
on the controller board
Check the sensor temperature/pressure on the LED moni-
tor.
(15)
Thermistor mounting problem (TH3, TH7)
Check the sensor temperature/pressure on the LED moni-
tor.
(16)
Disconnected male connector on the pressure switch (63H1) or dis-
connected wire
(17)
Open phase in the power-supply due to improper power-supply wiring
Refer to item (6) in section [6-1 Read before Test Run].
0000006452.BOOK 13 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......