[4-2 Outdoor Unit Circuit Board Components ]
10 -
chapter 4
BS_04_L
4 Ele
c
tr
ic
al
Comp
onen
ts
a
nd Wiring Diagra
ms
(2) PURY-(E)M350, (E)M400, (E)M450YNW-A1
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the voltage across pins 1 and 5 of connector RYPN has dropped to 20 VDC or less. It takes about 10 minutes to discharge
electricity after the power supply is turned off.
2) A Faston terminal on the inrush current resistor has a locking function. Make sure the cable heads are securely locked in
place. Press the tab on the terminals to remove them.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4)
Perform the service after disconnecting the relay connector (RYFAN1, RYFAN2). Before plugging in or unplugging
connectors, check that the outdoor unit fan is not rotating and that the voltage across pins 1 and 5 of connector
RYPN is 20 VDC or less. The capacitor may collect a charge and cause an electric shock when the outdoor unit fan
rotates in windy conditions.
Refer to the wiring nameplate for details.
5) After servicing, reconnect the relay connector (RYFAN1, RYFAN2) of the fan as it was.
6) When the power is on, the compressor or heater is energized even while the compressor is stopped. Before turning on the
power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the
compressor. Check the compressor for a ground fault. If the insulation resistance is 1.0 M
Ω
or below, connect all power supply
wires to the compressor and turn on the power to the outdoor unit. It is energized to evaporate the liquid refrigerant that has
accumulated in the compressor.
SC-W
Inverter output (W)
SC-V
Inverter output (V)
SC-U
Inverter output (U)
SC-L3
Input (L3)
SC-L2
Input (L2)
SC-L1
Input (L1)
CN2
Serial communication signal
Signal input
GND (MAIN circuit board)
Signal output
GND (MAIN circuit board)
CN19V
18 VDC
GND
CNCT2
Connects to ACCT
with lead wire
LED4
Lit: Microcomputer is energized.
Unlit: Microcomputer is not energized.
LED1
Lit: Inverter operation
Blinking: Inverter error
CNRY
12 VDC
GND (Power-supply board)
0000006414.BOOK 10 ページ 2021年10月12日 火曜日 午後4時43分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......