background image

Model

DCM601A51
DCM601A52
DCM601A53
DCM002A51
DCM008A51
DCM009A51

User’s Manual

Summary of Contents for DCM601A51

Page 1: ...Model DCM601A51 DCM601A52 DCM601A53 DCM002A51 DCM008A51 DCM009A51 User s Manual...

Page 2: ...at you can refer to it whenever necessary If the equipment is transferred to a new user be sure also to hand over the manual About intelligent Touch Manager WARNING Do not modify or repair the product...

Page 3: ...igent Touch Manager where there is a risk of moisture If moist gets into the product there is a risk of causing damage to internal electronic compo nents in addition to electric shocks Ensure that the...

Page 4: ...erned and ventilate the room and contact your Daikin dealer Do not use the air conditioner until a qualified service person confirms that the leakage has been repaired Do not operate the air condition...

Page 5: ...gen depletion Note that when the air conditioner is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentra t...

Page 6: ...tlet The containers may explode because the warm airflow from the indoor or outdoor unit will affect them Do not touch the motor parts at the time of filter replacement The motor in operation is at hi...

Page 7: ...uch as a burner is used together with the air conditioner Perform ventilation from time to time Insufficient ventilation may result in oxygen deficiency Be careful when using the air conditioner with...

Page 8: ...erable atmospheric oil such as in cooking areas g Where there are machines generating electromagnetic radiation h Where the air contains acidic or alkaline steam or vapour Protection against snow For...

Page 9: ...Management Points 27 2 2 Displaying Areas and Management Points 27 2 3 Starting Stopping Areas and Management Points 28 2 4 Setting up the Operation Mode for an Indoor Unit 29 2 5 Setting up the Setp...

Page 10: ...5 1 Setting up a Schedule 67 Setting up a schedule program 68 Detailed screen and button descriptions 79 5 2 Setting up the Timer Extension 107 5 3 Setting up the Auto Changeover 109 Creating and edit...

Page 11: ...ion Steps 147 Data Conversion 148 7 3 Outputting Function Settings 150 Operating Optional Functions 151 8 Setting up Automatic Control Functions 151 8 1 Setting up the Setback 151 8 2 Setting up the I...

Page 12: ...up the Energy Type Setting up Energy Groups 236 Setting up the Planned Energy Consumption Setting up the Actual Energy Consumption 243 11 3 Checking the Budget to Actual Energy Consumption 247 11 4 E...

Page 13: ...ng 290 14 1 Before Having the Product Serviced 290 14 2 Turning ON OFF the Internal Battery 301 14 3 Error Information Function 302 15 Hardware Specifications 304 15 1 iTM Hardware Specifications 304...

Page 14: ...computers in a LAN you can set up Web Remote Management and allow a maximum of 4 managers and 16 users to simultaneously access the iTM and if a connection to the Internet is available then you can m...

Page 15: ...3 2 1 Cautions when monitoring operating a Chiller management point A Chiller management point can read and write the specific objects on a MicroTech III controller POL687 70 MCQ which is embedded in...

Page 16: ...management point type 5 The management points D3Chiller Inv Chiller and Chiller are treated as the Chiller management points type 6 The management points BACnet Mi and BACnet Mo are treated as the Mul...

Page 17: ...gement point 1F North Building A 1F South Meeting Room Level 1 Level 2 Level 3 Level 4 Level 10 Management point A Aisle Management point A Management point A Aisle All Top Indoor Ventilator Indoor A...

Page 18: ...dged items as this could damage the touch screen permanently 3 1 3 3 2 3 8 6 Standard View Icon Screen 5 4 5 7 Detailed Setup dialog The following describes how the text on each component displayed on...

Page 19: ...appear when there are hidden lines and columns To display hidden lines and columns press or slide the scroll bars Truncated column text is displayed in a tool tip When sorting is enabled touch the he...

Page 20: ...ting a component that is not selectable is not possible is displayed on buttons and the like when the label text is truncated due to space availability To display the label text completely touch the c...

Page 21: ...atus When the list opens upward Open status When a row is selected 7 Text box Text box When unfocused Text box When focused Cursor Indicates the position where the next character will be entered 8 Spi...

Page 22: ...buttons Key buttons for entering characters 2 Input area text box Displays the entered characters For the Password input dialog it displays asterisks 3 Shift key toggle button Toggles between upper a...

Page 23: ...e maximum permitted Missing Indicates the number of characters still necessary to comply with the minimum required 6 Input switch combo box Toggles the keyboard between Special and Alph nm ltrs Specia...

Page 24: ...set as the iTM display language a button to display the input list appears Touch the button to display a list of frequently used words and select the word to input Select a word and commit the selecti...

Page 25: ...locale setting 3 Up Down button Increases or decreases the numeric value selected in the input area text box 2 by 1 10 1 or 10 4 AM PM setting combo box Specifies whether the time is AM or PM when ti...

Page 26: ...ive 4 Back button Deletes one digit at a time from the last number displayed in the input area text box 5 Clear button Completely deletes the numeric value displayed in the input area text box 6 Up Do...

Page 27: ...ntelligent Touch Manager 26 9 Input range label Displays the range of values that can be entered 10 OK button Touching this button commits the input 11 Cancel button Touching this button cancels the e...

Page 28: ...ea and indoor unit names the operation mode setpoint and fan speed information appears For detailed operation see 4 3 Standard View List Screen 2 2 Displaying Areas and Management Points 1 2 1 Display...

Page 29: ...Selecting Start in the On Off combo box starts the selected area or management point while selecting Stop stops the selected area or management point The icon turns green or red depending on the syst...

Page 30: ...h you want to set up the operation mode 2 Touch the Setting button and display the Detailed Setup screen 3 Select the A C tab 4 Select the Operation Mode check box and select Fan Cool Heat Dependent A...

Page 31: ...up the setpoint fan speed and airflow direction 2 Set up the setpoint in the Setpoint spin box and the Fan Speed using the buttons Low Middle High Automatic Available fan speed settings depend on the...

Page 32: ...d Setup screen 5 Select the A C tab 6 Select the Airflow Direction check box and set up the Airflow Direction using the buttons Air ow direction 0 Air ow direction 1 Air ow direction 2 Air ow directio...

Page 33: ...and display the Detailed Setup screen 3 Select the R C Prohibition tab 4 You can permit prohibit the following remote controller operations a start stop b set up the operation mode and c set up the s...

Page 34: ...or Bypass from the combo box 5 Select the check box for Ventilation Amount and select Auto normal Low normal High normal Auto fresh up Low fresh up or High fresh up from the combo box 6 Touch the OK b...

Page 35: ...enu List screen 2 Touch the Schedule button and display the Schedule screen 3 Select the schedule program to check 4 Touch the Confirm button on the Schedule screen and display the Confirm screen 5 Se...

Page 36: ...creen 3 Check settings in the Area List For detailed operation see 6 1 Naming and setting up the detailed information of an area Checking settings such as Mgmt Point Name Detailed Info and Icon 1 2 3...

Page 37: ...the Time DST Setup screen 3 On the screen the current time is displayed To change touch the Modify button 4 Enter the time in the Time Setup dialog that appears 5 Touch the OK button 6 Touch the OK b...

Page 38: ...nd buttons to specify the date for which you want to check the history Alternatively you can display the Time Setup dialog by touching the Modify button and specify the date there 4 Enter the time in...

Page 39: ...e cover To close the cover set it to Back Be careful not to touch the switch inadvertently 4 BACKUP Power ON OFF switch for settings backup battery Be careful not to touch the switch inadvertently 5 D...

Page 40: ...mission occurs on the DIII NET communication line 9 MONITOR key LED Orange Green Press this switch to turn on off the monitor Doing so also causes the LED color to change as follows Off Indicates that...

Page 41: ...Displays the list of menu items Sets up weekly and annual schedules Sets up a weekly schedule for each day Sets up schedules for special days such as extra holidays Sets up the off timer to prevent fa...

Page 42: ...y emergency stop program Function for keeping the room temperature within a certain range Function for controlling the indoor unit s setpoint in accordance with the outdoor temperature Function for au...

Page 43: ...tion Mgmt and Energy Navigator optional tabs The button changes to Close while the Menu List screen is being displayed 3 Standard View switch button Switches from the Layout View screen optional to th...

Page 44: ...red into waiting for release status automatically without the icon being touched even once The balloon is not displayed if the target unit was put into waiting for release status manually by touching...

Page 45: ...ment point 15 On Off Combo box Starts Stops the selected area or management point In the case of the system with Hydrobox 15 is only valid to operate the air conditioners To start stop the water heate...

Page 46: ...s for which manual setup is prohibited you can only reset the filter sign Setting items of functions not available for the management point being set up do not display NOTE Common Tab Sets up items co...

Page 47: ...abled Prohibited Disabled In the case of the system with Hydrobox choosing Stop Only or Prohibited makes the water heater to operate as Permitted NOTE 2 Operation Mode Sets up whether changing the ope...

Page 48: ...e follows the Cool or Heat operation mode set up in the air conditioner with Changeover option To select the Dry operation mode you need to complete the initial setup Some air conditioner models do no...

Page 49: ...iction Use this setting to limit the setpoint range that can be achieved Cooling Limit Sets up the setpoint range for the indoor unit in cooling mode Enable or disable and enter the maximum and minimu...

Page 50: ...ation Mode Select and set up a ventilation mode from Automatic ERVentilation and Bypass This setting may not be available depending on the model NOTE 2 Ventilation Amount Select and set up a ventilati...

Page 51: ...M to output a current voltage corresponding to the adjustment value from external equipment It is used for the adjustment of building equipment such as degree of aperture of a damper valve The range i...

Page 52: ...g the trial You cannot set MultiState in the area NOTE HW Supply Tab Sets up the Hydrobox Change settings by selecting the relevant check boxes 1 2 3 1 On Off Reheat Sets up whether starting stopping...

Page 53: ...ID field Displays the ID of the area or management point 3 Detailed Type field Displays the type of the area or management point 4 Port No field Displays the port number to which the management point...

Page 54: ...s of Automatic Ctrl System Settings Operation Mgmt and Energy Navigator optional tabs 3 Standard View switch button Switches from the Layout View screen optional to the Standard View screen 4 Layout V...

Page 55: ...s the screen to a view in which settings of areas and management points are displayed using icons 11 Information button Displays the legend for an icon or contact information for inquiries regarding t...

Page 56: ...e indoor unit of the selected area or the selected indoor unit Low Middle High Automatic 18 Setting button Displays the Detailed Setup screen for the selected area or management point 19 Header Each t...

Page 57: ...List switch button Switches to the Menu List screen which consists of Automatic Ctrl System Settings Operation Mgmt and Energy Navigator optional tabs 2 Standard View switch button Switches from the...

Page 58: ...ope and drag 12 Layout selection list The title selected in this list is the displayed layout 13 Back button Displays the previous screen again 14 Information button Displays the legend for an icon or...

Page 59: ...enabled Automatic Ctrl Tab 1 2 8 9 3 4 5 6 7 For an optional function its button is hidden unless the option is enabled NOTE 1 Schedule Allows you to set up weekly as well as annual schedules includin...

Page 60: ...outdoor temperature to keep the difference between the outdoor and indoor temperatures within a certain range It only works in Cool mode 7 HMO Optional function This function automatically starts stop...

Page 61: ...et up to 10 hierarchical levels 2 Mgmt Pts Changes the name detailed information and icon of management points 3 Maintenance Sets up a management point maintenance 4 Network Sets up the network IP add...

Page 62: ...alibration Corrects the contact points of the touch panel 11 Time DST Sets up the current time and the daylight saving time 12 Regional Sets up the language to use date and time format unit of tempera...

Page 63: ...l information etc You can also save history data to the folder on a USB memory 2 PPD Optional function This function calculates and displays the proportional distribution to each air conditioner of th...

Page 64: ...al consumption over the planned energy consumption per year month on a graph and the like You can also compare this year s actual consumption with that of last year s 2 Equipment op Mgmt This function...

Page 65: ...see 4 2 Standard View Icon Screen and 4 3 Standard View List Screen or the Information button 14 on the Layout View screen see 4 4 Layout View Optional Screen The Information screen consists of the Le...

Page 66: ...e is at least one management point with communication error in the area When there is at least one management point in emergency stop in the area When all management points are in mainte nance in the...

Page 67: ...User s Manual EM11A015B intelligent Touch Manager 66 Contact Tab 1 1 Displays contact information set up by the service person...

Page 68: ...unit Indoor Hydrobox AHU Ventilator Ventilator Chiller D3Chiller Inv Chiller Chiller Dio D3Dio External Dio BACnet Dio Analog Ao External Ao BACnet Ao MultiState Mo BACnet Mo Area All Target manageme...

Page 69: ...urday and Sunday Holiday 9 00 Off Every month 3rd Saturday only 9 00 to 18 00 Setpoint 28 C Cool On Creating the Weekly Schedule Create the weekly schedule Cool Office A to setpoint 28 C Monday to Fri...

Page 70: ...ies tab to display the Input dialog for entering the program name Enter Program for Office 2 Setting up the operation start time on Monday Touch to display the Weekly Pattern tab 3 4 Select Monday usi...

Page 71: ...70 5 Touch the Create button 5 to display the Events New program screen 6 7 Touch the Modify button 6 and display the Time input dialog to specify the operation start time Enter 9 00 AM9 00 when usin...

Page 72: ...ts of two tabs Mgmt Point and Area Touch and display the Area tab Select Office A from the list and touch the OK button to return For the procedure for creating areas see 6 1 Setting up an Area 4 Sett...

Page 73: ...hen the Setpoint radio button 11 Touch the Modify button Enter 28 in the Numerical Input dialog and touch the OK button to return to the A C tab Events screen Touch the OK button and return to the Eve...

Page 74: ...n exact copy of the selected event will appear Touch the Modify button 13 and enter the operation stop time 18 00 PM6 00 when using 12 hour clock in the Time Setup dialog Touch the OK button to return...

Page 75: ...ent set up for Monday to the other days of the week Select Monday then touch the Copy button 15 to display the Copy to Selection screen 16 Select the copy destination from the list 16 Select Tuesday W...

Page 76: ...of the weekly schedule Cool Office A to setpoint 28 C Monday to Friday from 9 00 to 18 00 Create the weekly schedule Stop air conditioning of Office A on Saturday and Sunday In the same way as 5 Setti...

Page 77: ...ton 18 to display the Name Input dialog Enter Working day for name and touch the OK button to rename the special day 2 Setting up the operation start stop times operation mode and setpoint Touch the E...

Page 78: ...f the week Saturday Touch the Add button to register the special day pattern It appears in 22 To preview the calendar with the special day pattern touch the Preview button 23 Touch the Close button an...

Page 79: ...n the Schedule Edit screen 24 Select the Enable radio button 24 and enable the Program for Office This completes the creation of the schedule program Touch the OK button to save and return to the Sche...

Page 80: ...y a calendar 5 1 3 4 2 6 7 8 9 10 11 1 Schedule Info view area Displays registered schedule programs 2 Selected schedule view area Displays information of the program selected in the Schedule Info vie...

Page 81: ...elected in the Schedule Info view area Touching the button displays a deletion confirmation dialog 9 Edit button Displays the Schedule Edit screen that allows you to edit the program selected in the S...

Page 82: ...d schedule view area Displays information of the program selected in the Schedule Info view area 3 Icon button Switches the screen to Icon view 4 Information button Displays the Legend screen 5 Create...

Page 83: ...displays a deletion confirmation dialog 9 Edit button Displays the Schedule Edit screen that allows you to edit the program selected in the Schedule Info view area 10 Calendar Copy button Displays th...

Page 84: ...view 1 Icon Displayed information Icon of scheduled program Validity period of scheduled program Upper Left Start date Lower right End date Name Icon type Disabled Without validity period With validi...

Page 85: ...ule Settings list Displays the list of events for the date indicated in the Date area 2 for the selected schedule program 2 Date area Displays the date and day of the week for which the events are dis...

Page 86: ...me using 1 to 32 characters irrespective of single or double byte Duplicate names are not permitted 2 Activation radio button Enables disables the schedule program 3 Period check box combo box Selecti...

Page 87: ...e set for the day of the week selected with the radio button will be copied 4 Delete button Deletes the schedule set to the day of the week selected with radio button Touching the button displays a de...

Page 88: ...o Selection screen that allows you to select the destination to which the schedule set for the special day selected with the radio button will be copied 4 Delete button Deletes the schedule set to the...

Page 89: ...ds available in the Schedule Settings view area SB Low and SB High are displayed only when the optional setback function is enabled 8 OK button Saves the edit and closes the screen 9 Cancel button Can...

Page 90: ...aximum of 40 special day patterns in one calendar 2 button Moves up and down the order of the special day pattern selected in the Calendar Settings list 3 Delete button Deletes the special day pattern...

Page 91: ...day pattern 8 Preview button Previews the calendar with the registered special day in the Calendar Settings list 9 OK button Saves the edit and closes the screen 10 Cancel button Cancels the edit and...

Page 92: ...st takes precedence If two or more special days set using the Month Day setup combo box overlap the latter lower in the list takes precedence Setting up a Special Day overrides the weekly schedule set...

Page 93: ...o select the destination of the copy 3 Preview radio button Selects the schedule to be displayed in the Calendar view area You can select the schedule program source of the copy or a schedule program...

Page 94: ...ed in the Schedule Edit screen 3 Back button Moves the Event list view to that of the previous day of the week special day 4 Next button Moves the Event list view to that of the next day of the week s...

Page 95: ...User s Manual EM11A015B intelligent Touch Manager 94 9 OK button Saves the edit and closes the screen 10 Cancel button Cancels the edit and closes the screen...

Page 96: ...to copy events set up for a day of the week special day to another day of the week special day 2 3 4 1 1 Copy from text field Displays the name of day of the week special day selected in the Schedule...

Page 97: ...96 Event Screen This screen consists of six tabs Common R C Prohibition A C Ventilator Ao Mo and HW Supply each outputting different event actions Setting items of functions not available for the mana...

Page 98: ...he time in the Time Input dialog that appears The range of values you can enter is 00 00 to 23 59 AM00 00 to PM11 59 when using 12 hour clock 2 Mgmt Pnt Area setting area Sets up the management points...

Page 99: ...to commit the setting Pre cool Pre heat function is a function that starts the air conditioners earlier than the time set up in the schedule to make the room temperature reach the setpoint at the set...

Page 100: ...and the normal schedule will be executed When restarting iTM If iTM is restarted pre cool heat scheduled on the day of restart will be ignored and the normal schedule will be executed Execution of pre...

Page 101: ...ontroller Select the setting from Permitted Stop Only and Prohibited 2 R C Operation Mode permission prohibition setting area Restricts changing the operation mode from the remote controller Select th...

Page 102: ...on or b Setpoint shift radio button If you selected Setpoint touch the Modify button and enter the temperature in the Numerical Input dialog that appears The range of values you can enter is 30 to 70...

Page 103: ...ving water setpoint NOTE 3 Leaving Water Setpoint Cool Sets up the outlet water temperature in cooling Touch the Modify button and enter the water temperature in the Numerical Input dialog that appear...

Page 104: ...n the Numerical Input dialog that appears The range of values you can enter is the same as that for the Setpoint 2 but the entered values should be such that they do not invert the upper and lower lim...

Page 105: ...et up and select the setting from the combo box 1 Ventilation Mode setting area Sets up the ventilation mode Select the setting from Automatic ERVentilation and Bypass 2 Ventilation Amount setting are...

Page 106: ...ut a current voltage corresponding to the adjustment value from external equipment It is used for the adjustment of building equipment such as degree of aperture of a damper valve The range incrementa...

Page 107: ...tab on the Events screen It allows you to set up the Hot water supply actions 1 Select the check box of the items to set up and select the setting using the combo box radio buttons 1 Low Noise setup...

Page 108: ...e counted Duration will be cleared In the case of the system with Hydrobox this function cannot control the reheat start operation but only that of air conditioners NOTE 1 Touch the Timer Extension bu...

Page 109: ...aneously set up the air conditioners may be stopped before the time set up by this function preventing the temperature to reach the setpoint at the set time Example 1 Duration is set to 30 minutes 2 P...

Page 110: ...setpoint is changed an assessment is performed immediately and then once every 5 minutes The assessment of the control condition is performed according to the following four patterns depending on the...

Page 111: ...is 2 C Cooling mode Heating mode Heating mode Cooling mode Heating mode Heating mode Cooling mode Representative suction temperature When Representative suction temperature Representative setpoint Hea...

Page 112: ...tative setpoint Cool Thermal difference in 0 C 1 5 When the thermal difference is 0 C Heating mode Cooling mode Cooling mode Heating mode Heating mode Heating mode Cooling mode The following describes...

Page 113: ...a management point that is not registered in any group based on the affiliation information displayed in 7 Selecting a management point from 6 and touching the Remove button cancels its registration...

Page 114: ...113 Setting up the changeover conditions 9 10 1 Select a group in 9 and touch the Attributes button 10 to display the Attributes dialog box 11 12 13 2 Touching the Modify button in 11 displays the Nam...

Page 115: ...In this mode information of the indoor unit registered at the top is used even when that indoor unit is stopped However this function does not work if the operation mode of that indoor unit is other...

Page 116: ...button 15 To disable select Disable Cautions when Using Simultaneously with Other Control Functions 1 If the cooling setpoint is lowered by the Sliding Temperature function when this function is set u...

Page 117: ...as intended with the settings Example When the method for referencing room temperature and setpoint is set up to Fixed and the thermal difference to 4 C 1 Heating starts with setpoint for the indoor...

Page 118: ...intenance you can recover the iTM forcibly The following describes how to interpret the Emergency Stop view and release an emergency stop If the optional function is enabled you can divide the emergen...

Page 119: ...ct the program to release and touch the Release button 4 Only Default is displayed for programs if the optional function is disabled When the Confirm dialog appears touch the Yes button to release the...

Page 120: ...the Menu List screen and display the Area Setup screen see 4 5 Menu List screen System Settings Tab Fig 1 Area Management point 1F North 1F South Meeting Room Aisle Room A Room B Of ce Lighting A Buil...

Page 121: ...ly created area is created under existing management points and areas You will not be able to create new areas in the following cases The number of areas exceeds 650 The area selected in the Area List...

Page 122: ...touch the Delete button 4 Touching the YES button on the deletion confirmation dialog that appears deletes the selected area 1F North 1F South Aisle Of ce Lighting A Lavatory Building A Top All Indoor...

Page 123: ...p All Indoor Ventilator Fig 5 5 1 To move an area select the area you want to move for example Meeting Room and touch the Move button 5 to display the Area Move screen The area to move and lower level...

Page 124: ...button 1F North 1F South Aisle Lighting A Lavatory Building A Top All Indoor Ventilator Fig 6 Of ce Meeting Room Room A Room B 3 The moved area for example Meeting Room is displayed under the area sel...

Page 125: ...e Area Member Registration screen 7 9 10 8 1 1 00 Indoor 1 1 01 1 1 02 1 1 03 1 1 04 1 1 05 Room A Fig 8 2 The list 7 displays management points and areas directly under the area being edited in the o...

Page 126: ...10 for changing the order of members displayed in 7 at once Selecting a management point or area for example 1 1 04 to move and touching the Jump button 10 displays the Order Setup screen You can sele...

Page 127: ...an area 12 1 Select the area to name and set up the detailed information from the Area Setup screen and touch the Attributes button 12 to display the Area Attribute Setup screen 13 14 2 Touch the Modi...

Page 128: ...gement points and areas in the order they are listed in the Area Member Registration screen 15 16 1 Touch the Modify buttons 15 and 16 on the Area Attribute Setup screen Enter the interval for startin...

Page 129: ...elligent Touch Manager 128 Setting up icons 17 1 Touch the Modify button 17 on the Area Attribute Setup screen to display the Icon Setup screen 2 Select an icon from the displayed icon list and touch...

Page 130: ...save area data in CSV format Max Time 15 sc will appear Touch the Yes button to save When successfully saved the message File has been saved will appear 2 To load connect the USB memory with the CSV...

Page 131: ...following describes how to set this up 1 Touch the Mgmt Pts button on the System Settings tab of the Menu List screen and display the Mgmt Points Setup screen see 4 5 Menu List Screen System Settings...

Page 132: ...Same Mgmt Point name is already registered appears and it is rejected Touch the Modify button 5 for Detailed Info Enter the detailed information in the Text Input dialog that appears The maximum numbe...

Page 133: ...ton and display the Password dialog to enter the password for unlocking the screen When administrator password and screen lock are simultaneously enabled entering the administrator password after touc...

Page 134: ...Screen Lock select Enable in 2 To disable select Disable Selecting Enable displays the Password dialog for entering a new password Set a password using 1 to 15 alphanumeric characters The dialog will...

Page 135: ...this function up 1 Touch the Maintenance button on the System Settings tab of the Menu List screen and display the Maintenance Settings screen see 4 5 Menu List Screen System Settings Tab 2 1 2 To se...

Page 136: ...tor style and icon color used in the iTM unit 1 Touch the Regional button on the System Settings tab of the Menu List screen and display the Locale screen see 4 5 Menu List Screen System Settings Tab...

Page 137: ...4 Select the temperature unit from Fahrenheit and Celsius using the Celsius Fahrenheit radio button 5 Select the decimal point CSV file separator style using the Decimal Point CSV Separation radio but...

Page 138: ...ton and close the screen Entering an inappropriate value displays an error dialog where you will be able to enter the correct value 3 When using daylight saving time enable it in 3 and select the star...

Page 139: ...electing Backlight Off will turn off the screen when the idle time set in step 3 elapses Touch the Preview button 2 to preview the selected screensaver Touch the screen to return to the Screensaver sc...

Page 140: ...ettings Tab 1 2 3 2 In the Screen Luminance combo box 1 select and set the luminance level for the iTM screen to a value between 1 and 8 3 In the Buzzer combo box 2 select and set the volume for the b...

Page 141: ...top operation from the iTM s Standard View screen Con rmation dialog 1 Touch the Confirmation Dialog button on the System Settings tab of the Menu List screen to display the Confirmation Dialog screen...

Page 142: ...calibration screen see 4 5 Menu List Screen System Settings Tab 1 2 A cross 1 will appear 5 times on the screen Touch the center of each cross in order You can start the calibration again by touching...

Page 143: ...pecifications CB14A005 1 Touch the Backup button on the System Settings tab of the Menu List screen see 4 5 Menu List Screen System Settings Tab 2 When the dialog that confirms the start of the backup...

Page 144: ...d is as indicated below 1 Touch the Version Info button on the System Settings tab of the Menu List screen to display the Version Information screen see 4 5 Menu List Screen System Settings Tab 1 2 3...

Page 145: ...ist Screen Operation Mgmt Tab A Wait dialog is displayed while the history is being acquired NOTE 1 3 4 5 6 2 2 1 displays the latest 100 history records Touch the button in 2 to display the previous...

Page 146: ...utton 6 to display the History Output screen 7 8 7 4 Touch the Modify button 7 and display the Data Input dialog to specify the output period of the CSV file Touching the Output button 8 displays a co...

Page 147: ...pecifications CB14A005 The following output data must be converted into the CSV format History data Energy Navigator Energy data Management point data Failure to turn off data Setpoint gap data Data o...

Page 148: ...using the Web Remote Management function option you can save data in a compressed format zip via the Web browser on your PC Unzip the compressed files and go to step 3 Operation on PC 2 Connect the US...

Page 149: ...the iTM on your PC 1 The folder name varies depending on the output data NOTE 2 Double click CSVOutputTool exe 1 to start the CSV output tool Data conversion starts During data conversion the CSV Out...

Page 150: ...at in the folder The saved CSV filename varies depending on the output data The display order of the year month and day depends on the date display format selected in the locale time zone daylight sav...

Page 151: ...ttings of programs registered with the Auto Changeover Temperature Limit Settings of groups registered with the Temperature Limit Sliding Temperature Settings of groups registered with Sliding Tempera...

Page 152: ...or both depending on your needs Setpoint Time During absence During presence During absence Setup setpoint upper limit setpoint during absence lower limit setpoint during absence Cool setpoint during...

Page 153: ...ive Setback Setpoint the indoor unit is stopped 2 Room temperature is continuously monitored and when it becomes lower than the Setpoint Relative Setback Setpoint the indoor unit is started again 3 Th...

Page 154: ...unit is stopped by the Timer Extension function when setback is active NOTE The following describes how to set this up 1 Touch the Temp Setback button on the Automatic Ctrl tab of the Menu List scree...

Page 155: ...Select the temperature for heating in the Heat Setback Recovery Temp combo box 7 The range of values you can select from is 1 to 6 C in increments of 1 C When finished touch the OK button to return t...

Page 156: ...ng the function may also not work even if a higher value than the Relative Setback Setpoint or Relative Setup Setpoint is set Temperature Limit Since Temperature Limit is a function that works when th...

Page 157: ...Setback Inactive Not treated as OFF Sliding Temperature HMO Setback Active Not treated as ON Setback Inactive Treated as OFF Timer Extension Start order by Setback Not treated as start trigger Stop or...

Page 158: ...hen the status specified as the required condition continues for a specified time and outputs the specified actions to the target management points or areas The management point types and conditions t...

Page 159: ...n as an expression 2 For the explanation of the required duration see Example Delay ON timer 15 min example on the next page Example If required duration is set to 15 minutes whether the condition has...

Page 160: ...io D3Dio External Dio BACnet Dio Analog Ao External Ao BACnet Ao MultiState Mo BACnet Mo Area All Target management point type Operation Mode Setpoint Setpoint shift Leaving Water Setpoint Target mana...

Page 161: ...rt The initial status of a target input management point when started is handled as unfixed Similarly to the case above the changes in status before and after unfixed are not viewed as triggers of suc...

Page 162: ...ly show unexpected behavior Example When the program is set as follows Input 1 00 1 01 Output 1 One input status change 1 02 turns ON Output 2 All inputs status change 1 02 turns OFF Required duration...

Page 163: ...nput is On 1 03 turns ON Required duration 0 min 1 00 Operating On Stopped Off 1 01 Operating On Stopped Off 1 02 Operating On Stopped Off 1 03 Operating On Stopped Off Interlocking control is execute...

Page 164: ...er indoor unit a or indoor unit b goes on turn on Ventilator c The required duration is 10 minutes Output2 When both indoor unit a and indoor unit b go off turn off Ventilator c Creating the Interlock...

Page 165: ...ection Condition combo box 4 displays a list of management points 5 for which On Off can be registered as the condition to be detected Selecting the indoor unit a and touching the Add button registers...

Page 166: ...the Interlock Program Input screen Similarly set up the indoor unit b 9 Select the indoor unit a and touch the Timer min button 9 and enter 10 for required duration in the Numerical Input dialog that...

Page 167: ...indoor unit a or b to be On for 10 minutes 4 Setting up the target Touch the Modify button 12 and display the Interlock Program Output Setup screen 14 15 13 13 is the list of management points and are...

Page 168: ...select the Start radio button Touch the OK button and return to the Interlock Program Output Setup screen Touch the OK button and return to the Interlock Program Setup screen The step above finishes t...

Page 169: ...17 and then All inputs become invalid in the Input condition combo box 18 Touch the Modify button 19 and display the Interlock Program Output Setup screen 21 22 20 Select Ventilator c from 20 and tou...

Page 170: ...lect the On Off check box 23 select the stop radio button and touch the OK button to return to the Interlock Program Output Setup screen Likewise touch the OK button on the Interlock Program Output Se...

Page 171: ...ff The Ventilator control program is now complete Touch the OK button and return to the main Interlocking Control screen Enabling the Interlocking Program Enable the created interlocking program 24 Se...

Page 172: ...ist Displays registered interlocking programs 2 Activation area Enables and disables an interlocking program 3 Create button Creates a new interlocking program Touching the button displays the Name In...

Page 173: ...s the program selected in the interlocking program list Touching the button displays the Text Input dialog 7 Edit button Displays the Interlock Program Setup screen that allows you to edit the program...

Page 174: ...nput becomes valid All inputs become valid At least one input becomes invalid and All inputs become invalid 5 Modify button Output Displays the Interlock Program Output Setup screen that allows you to...

Page 175: ...increments of 1 second It is 1 to 30 seconds when the Detection Condition is Analog value 3 Condition Setup button Displays the Condition Setup screen that allows you to set up the conditions require...

Page 176: ...Points list to the Management Point Input list You can register up to 50 management points to monitor However you cannot register areas 7 Remove button Removes the management point selected in the Man...

Page 177: ...en opens on the tab that corresponds to the type of the monitored management point Start Stop Error Tab Condition Setup Screen This screen is displayed when you touch the Start Stop Error tab on the C...

Page 178: ...Condition Setup screen Sets up the conditions required for the operation mode to be detected 1 2 3 1 Operation Mode combo box Select the operation mode required for clearing the condition Select an o...

Page 179: ...e inequality sign to be used in the analog value condition from and 3 Analog Value2 setting area Sets up the right side of the analog value condition a Constant Value setting area Select this area whe...

Page 180: ...values you can enter see Appendix 2 Setup items 4 Hysteresis setting area Sets up the range of the dead zone Touch the Modify button and enter the range in the Numerical Input dialog that appears For...

Page 181: ...e In addition you can set a hysteresis around the valid invalid border value to prevent hunting In case that the condition is set between analog values the conditions can only be set to the management...

Page 182: ...ue Assessment Not assessed Previous assessment kept Analog value at the management point Analog value at the management point Assessment interval 1 minute Assessment interval 1 minute Failure Success...

Page 183: ...cept above Not assessed Previous assessment kept Analog value at management point 1 Analog value at management point 1 Success Failure Hysteresis Hysteresis Assessment interval 1 minute Assessment int...

Page 184: ...any inappropriate setting exists for example room temperature 200 C If an abnormal value is entered due to an analog sensor malfunction the analog value condition may be always cleared or not cleared...

Page 185: ...he action to be performed by the output event selected in the Events list 4 Available Management Points Area list Displays a list of management points areas to which events can be output 5 Add button...

Page 186: ...able for the management point being registered do not display NOTE Common Tab Action Setup Screen This screen is displayed when you touch the Common tab on the Action Setup screen Sets up actions for...

Page 187: ...ting using the radio buttons 1 Start Stop setting area Sets up whether starting stopping the management point from the remote controller will be permitted or prohibited 2 Operation Mode setting area S...

Page 188: ...etting area Sets up the setpoint To set up select either the a Setpoint radio button or b Setpoint shift radio button If you selected Setpoint touch the Modify button and enter the temperature in the...

Page 189: ...Sets up the outlet water temperature in cooling Touch the Modify button and enter the water temperature in the Numerical Input dialog that appears The range of values you can enter is 30 to 70 C 4 Lea...

Page 190: ...s to set up and select the setting from the combo box 1 Ventilation Mode setting area Sets up the ventilation mode Select the setting from Automatic ERVentilation and Bypass 2 Ventilation Amount setti...

Page 191: ...nding to the adjustment value from external equipment It is used for the adjustment of building equipment such as degree of aperture of a damper valve The range incremental width and unit of the analo...

Page 192: ...Tab Action Setup Screen Sets up the Hydrobox Change settings by selecting the relevant check boxes 1 2 3 1 Low Noise Enables or disables the Low Noise function 2 OK button Saves the edit and closes th...

Page 193: ...efault program cannot be edited except from toggling enable and disable If the optional Emergency Stop function is enabled you can create your own emergency stop program The following describes how to...

Page 194: ...name You can name the program using up to 20 characters Enter a name and touch the OK button to close the screen The program is added to the list 1 Then touch the Edit button 6 and display the Emergen...

Page 195: ...s the air conditioners only but unable to control the water heater operation NOTE 7 Using the Release Mode combo box 13 select the method of releasing the emergency stop program from Automatic and Man...

Page 196: ...Default program canceling the emergency stop signal input automatically releases the emergency stop Forcible release possible Programs created in this chapter can be manually released When a program i...

Page 197: ...limit room temperature 4 C or room temperature heat setpoint sends the order to stop Assessments following an order to start cooling or heating are not performed until after a period of 30 minutes Ho...

Page 198: ...ght 2 Create button Creates a new group and displays the Name Setup dialog that allows you to enter the name Duplicate names are not permitted You can create up to 8 Temp Limit groups Touch the OK but...

Page 199: ...d touch the Remove button The management points you can register are limited to indoor units You can register up to 512 indoor units in one group You cannot register the same indoor unit in multiple g...

Page 200: ...rical Input dialog In Upper Limit you can specify a temperature in the 32 C to 50 C range in increments of 1 C while in Lower Limit you can specify a temperature in the 2 C to 16 C range in increments...

Page 201: ...started and stopped every 5 minutes hunting depending on the setpoint Example When the setpoint for Sliding Temperature calculated from the outdoor temperature is 32 C and the upper limit for this fu...

Page 202: ...nt The outdoor temperature and setpoint are linked through the following expressions When the outdoor temperature is higher than the upper limit outdoor temperature Setpoint Upper limit setpoint When...

Page 203: ...the right 2 Create button Creates a new group and displays the Name Setup dialog that allows you to enter the name Duplicate names are not permitted You can create up to 8 Sliding Temperature groups T...

Page 204: ...and touch the Add button To remove a management point select one from 6 and touch the Remove button The management points you can register are limited to indoor units You can register up to 512 indoo...

Page 205: ...where you can change the group name Touching the Modify button 9 displays the Analog Input screen where you can register the Ai management point at which the outdoor temperature will be measured 10 S...

Page 206: ...in the 18 C to 34 C range in increments of 1 C while for lower limit outdoor temperature you can set a temperature in the 16 C to 32 C range in increments of 1 C When finished touch the OK button to...

Page 207: ...ing to the outdoor temperature 4 If the outdoor temperature decreases the setpoint is lowered up to 20 C by this function 5 When the room temperature further decreases and becomes 16 C the Auto Change...

Page 208: ...f suction temperature setpoint 1 C starts the indoor unit While stopped by this function if Heating Mode Optimization is changed from Enabled to Disabled in the Heating Mode Optimization Settings scre...

Page 209: ...screen Cautions when Using Simultaneously with Other Control Functions 1 Start stop of indoor units by this function becomes the input condition for the Interlocking Control function 2 Since indoor u...

Page 210: ...ication via E mail in the case of an error To use these functions you must set up the network on the iTM unit The following describes how to set this up 1 Touch the Network button on the System Settin...

Page 211: ...dialog that appears For information necessary for the settings consult your network administrator 1 Controller name 2 Host name 3 IP address 4 Subnet mask 5 Default gateway address 6 Preferred DNS ad...

Page 212: ...u change the settings in the Numerical Input dialog that appears Touch the OK button to close the screen The range of possible input port number see Appendix 1 iTM Monitoring Control Functions 4 When...

Page 213: ...erent ranges of operations permitted in accordance with their privileges For the PC requirements to use this function see Peripheral Equipment Specifications CB14A005 LAN port Broadband Router HUB Int...

Page 214: ...allowed to access up to 4 managers and 16 users simultaneously 1 Touch the Web Access Users button on the System Settings tab of the Menu List screen and display the Web Access Users Settings screen s...

Page 215: ...Input dialog Enter the same password twice for confirmation Set a password using 0 to 15 alphanumeric characters Select the type of user in 7 In the case of a user set up the Managed Area and Screen M...

Page 216: ...that can be registered Select a screen from 12 and touch the Add button to register it as the target Layout View screen You can only register one Layout View Select a registered screen from 11 and tou...

Page 217: ...box you cannot use some special characters In the Password text box you cannot use special characters On the Layout View Screen see 4 4 Layout View Optional Screen you can monitor management points a...

Page 218: ...r name and password in 13 and click the Login button 14 The Web Remote Management screen Icon view appears if authentication is successful 2 Entering the user name and password and clicking the User S...

Page 219: ...nfirmation screen that appears and log off Web Remote Management Screen Logoff button The operation after login is basically the same as from the iTM unit For the operating procedure see the relevant...

Page 220: ...User s Manual EM11A015B intelligent Touch Manager 219 Web user A has the Interlocking Control screen open Information dialog is displayed when the Web user B presses the Interlock button...

Page 221: ...t function does not support iTM specific functions screensaver hardware setup touch panel calibration to prevent incorrect setup of the iTM unit hardware The Web Remote Management function supports th...

Page 222: ...ver and a terminal for receiving E mails are necessary in addition to the iTM unit NOTE The following describes how to set this up Setting up the Mail Server Touch the E mail button on the System Sett...

Page 223: ...me will be used as subject of the E mails Select the E mail resending interval in the combo box 3 You may select an interval of 1 to 72 hours in increments of 1 hour If after sending the E mail once t...

Page 224: ...ministrator 5 URL or IP address of the SMTP Server 6 Port number of the SMTP Server 7 Authentication method for outgoing E mails Select one from No Authentication POP Before SMTP and SMTP AUTH 8 URL o...

Page 225: ...he relevant button on the right 13 Create button Creates a new E mail address Touch the button and enter an address of up to 128 characters in the E mail Address Setup dialog that appears 14 Delete bu...

Page 226: ...anagement point that will be target of monitoring from 17 and touch the Add button You can register up to 512 management points Selecting a management point from 16 and touching the Remove button canc...

Page 227: ...Site Name name SMTP Server Title SMTP Server Address Address address Port number Port port Authentication Authentication method Authentication Authentication method Authentication method is one among...

Page 228: ...User s Manual EM11A015B intelligent Touch Manager 227 Touch the OK button to send the trial e mail The screen returns to the E mail Address tab When finished touch the OK button to close the screen...

Page 229: ...t with the 3G USB modem 1 Insert the 3G USB modem into the iTM 2 Open Menu List after the LED of the modem becomes Green blink The light of LED on the modem indicate as below Red light No radio wave G...

Page 230: ...he controller is turned off Do not turn off the controller if calculating proportional distribution This chapter describes operations to be performed on the iTM unit The iTM is designed to measure the...

Page 231: ...the specified counting date does not exist in the month the counting period will be automatically adjusted to match the calendar dates Excluded Time Exceptions button 2 is the button for advanced set...

Page 232: ...for proportional distribution are not collected during excluded times This setting is normally unnecessary Set this up only when necessary and after a thorough check Excluded Time will be as indicted...

Page 233: ...nagement function Equipment operation management function Energy administrator Test Operation For calculation of the indoor unit power Data export function Service person Trial Energy Navigator Energy...

Page 234: ...t in the iTM implementation year and start managing the equipment operation the next year Check the actual opera tion for creating the operation plan The user performs a simple hypothesis testing on o...

Page 235: ...ption plan for the current year Check the measured actual energy consumption Check the actual opera tion for creating the operation plan The user performs a simple hypothesis testing on operational st...

Page 236: ...ctual visualization function Monthly energy budget actual visualization function Year to year energy comparison function Yes Yes Yes No No Yes Budget actual can be visualized by manually entering the...

Page 237: ...up the Energy Type Setting up Energy Groups Setting up the Energy Type Set up the energy type and energy group target of the energy budget actual management Display the Energy Navigator tab of the Me...

Page 238: ...A015B intelligent Touch Manager 237 2 Touch the Display mode button 2 and display the Display mode screen The Display mode button is available on all tabs 3 Touch the Modify button 3 and display the E...

Page 239: ...y type You can name the energy type using up to 16 characters 6 Copy button Creates a new energy type by copying the selected energy type Enter a name in the Name Input dialog that appears Touch the O...

Page 240: ...9 range in increments of 0 001 The unit is displayed in accordance with the energy type selected in 10 If a new energy conversion type is registered on the Energy Conversion Type Setup screen enter th...

Page 241: ...up target of energy budget actual management 15 is the list of Energy Groups Perform the intended operation by touching the relevant button on the right 16 Create button Creates a new Energy Group You...

Page 242: ...ou to set up the selected group 21 22 23 Set the management point from which to acquire the data to be used in energy budget actual management In an Energy Group you can only register Pi management po...

Page 243: ...button to save the settings and return to the Energy Group screen When finished touch the Close button to return to the Display Mode screen Touch the Close button on the Display Mode screen to close t...

Page 244: ...value 24 25 You can select a registered Energy Group using the Display item combo box 24 available on each tab of the Energy budget actual management screen Select the Energy Group to which to set th...

Page 245: ...previous year Select the unit for the objective setting in 29 Select either a Settings by year or b Settings by month When the objective is a by year touch the Modify button 30 and enter the reductio...

Page 246: ...In the Energy Type combo box 35 select the energy type for which to enter the actual energy consumption from Power Gas and Water You can select from the energy types included in the selected Energy Gr...

Page 247: ...nds on the selected energy type Touch the Modify button and enter the conversion factor in the Numerical Input dialog that appears You can enter a value in the 0 to 9999 999 range in increments of 0 0...

Page 248: ...en Energy Navigator Tab Yearly budget actual mgmt Tab Energy budget actual management Screen 1 7 4 6 2 3 5 This screen displays the yearly budget to actual energy consumption status for the Energy Gro...

Page 249: ...anned energy consumption exist Accumulated energy consumption Planned accumulated energy consumption 0 Excess over planned energy consumption kWh Accumulated energy consumption kWh Planned yearly ener...

Page 250: ...y consumption kWh Planned yearly energy consumption kWh Estimated energy consumption Planned accumulated energy consumption 0 Energy consumption plan achieved Nothing Estimated energy consumption kWh...

Page 251: ...type you will be able to select the total of CO2 emitted by all types of energy Selecting the unit of energy to display in the graph from Energy CO2 and new conversion type in the Energy Unit combo bo...

Page 252: ...kWh Caution Excess over target energy consumption Nothing kWh Estimated energy consumption kWh Target energy consumption kWh Danger Target energy consumption already exceeded Estimated energy consump...

Page 253: ...User s Manual EM11A015B intelligent Touch Manager 252 Results may not be displayed when there are missing actual and or planned values NOTE...

Page 254: ...it of energy to display in the graph from Energy CO2 and new conversion type in the Energy Unit combo box 17 plots the graph in 18 In the graph the horizontal axis represents each month of the year fr...

Page 255: ...ent of the energy consumption plan Also touching a month on the graph displays the actual energy consumption for that month and the previous year s actual value in a tool tip Message Accumulated actua...

Page 256: ...nction Yes Yes Yes No No Yes No No Engineering details Equipment operation management Trial Power Proportional Distribution Operation rules Failure to turn off sampling function Failure to turn off sa...

Page 257: ...week Monday to Sunday No special day settings Operating hours 9 00 to 21 00 AM9 00 to PM9 00 when 12 hour clock is used Setpoint Cool 24 C Heat 24 C The following describes how to set this up and use...

Page 258: ...r Rules button 3 and display the Operation Rule screen The Oper Rules button is available on both tabs 4 5 6 7 8 9 4 is the list of registered operation rules Perform the intended operation by touchin...

Page 259: ...ion rule 8 Rename button Renames the selected operation rule Enter a name in the Name Input dialog that appears Touch the OK button to change the name You can name the operation rule using up to 16 ch...

Page 260: ...the week to which you want to set up a rule Select the day of the week to edit from 10 11 is the content of operation rules 12 displays the legend Touch the Copy button 13 to copy the operation rule o...

Page 261: ...M00 00 to PM12 00 when using 12 hour clock range and in increments of 15 minutes If the entered value is not a multiple of 15 minutes a dialog is displayed and the value rounded to a multiple of 15 mi...

Page 262: ...can set up to 5 types of special day patterns Select the special day to edit in 19 The subsequent steps and screen interpretation are the same as for the Weekly Pattern Set up the operation rule usin...

Page 263: ...are as follows Month Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec and Every Day 1 to 31 However non existing days cannot be selected Week 1st 2nd 3rd 4th and Last Day of the week Sunday Monday Tues...

Page 264: ...he Calendar Copy screen 30 28 29 The name of the selected operation rule is displayed in 28 In 29 you can preview the operation rule calendar of both the source and destination of the copy Check by sw...

Page 265: ...erature Limit Pre Cool Pre Heat are exempt from the operation rules during their operating hours 2 Automatic control functions that work when there are people in the room Auto Changeover HMO Timer Ext...

Page 266: ...ed in the selected area are displayed The sampled information is presented in two tabs Failure to turn off tab where management points that were operating when they should be stopped are sampled and S...

Page 267: ...izontal axis represents the number of days on which failure to turn off occurred When displayed by area the total days on which the management points included in the area were not turned off is displa...

Page 268: ...mes Mgmt Point while in Area view Touching the button changes the view to Mgmt Point Selecting a management point from the list in Mgmt Point view and touching the Details button 8 displays the Detail...

Page 269: ...of the Date period is displayed by default You can change the date by touching the Next and Back buttons 10 is the operational status graph The horizontal axis represents time and the vertical axis t...

Page 270: ...s the list of dates on which deviations from the operation rule found in the selected management points The list displays the accrual dates accrual time and amount of energy consumed When finished che...

Page 271: ...ab this screen displays the operational status for the set sampling period sampling targets and operation rules The screen interpretation and steps are the same as for the Failure to turn off tab see...

Page 272: ...itions displayed on the current screen The data of top 50 management point area will be saved The name of the file to be output changes depending on the source tab as below Failure to turn off tab Mng...

Page 273: ...m the Equipment operation management screen For the PC USB memory requirements to use this function see Peripheral Equipment Specifications CB14A005 The following describes the steps to output the ene...

Page 274: ...and the last year Connect a USB memory to the iTM unit and touch the Save button In the confirmation dialog that appears touch the Yes button to start outputting data When save is complete a dialog ap...

Page 275: ...tton 3 In the confirmation dialog that appears touch the Yes button to start outputting data When save is complete a dialog appears Touch the Close button to close the screen The data is saved in MngP...

Page 276: ...tegrator to each iTM you can monitor operate and set up in the same way as with the iTM unit However the following are functions specific to the iTM unit and cannot be set up by accessing from the iTM...

Page 277: ...and displays its Standard View Icon screen 3 Information button Displays the legend for the Icon view and contact information for inquiries regarding the iTM integrator 4 Menu List switch button Swit...

Page 278: ...ew screen and access an iTM The Unlock Lock button that is usually displayed on the iTM unit is not displayed The iTM integrator can access an iTM unit even if its screen is locked 7 8 7 Controller na...

Page 279: ...elligent Touch Manager 278 Legend Tab Information Screen This screen is displayed when you touch the Information button on the iTM integrator Standard view screen It displays the legend of icons used...

Page 280: ...cation error When there is at least one management point connected to the iTM with error Error sign is displayed over the Operating Stop No operation When there is a system error in iTM 2 When there i...

Page 281: ...reen This screen is displayed when you touch the Contact tab on the Information screen Displays contact information set up by the service person Contact information displayed here are contacts regardi...

Page 282: ...egrator Standard view The setup method is the same as that of the iTM unit See 4 5 Menu List Screen Operation Mgmt Tab 1 1 History button Sets up history management of error occurrence status change c...

Page 283: ...ervers 2 Web Access Users button Sets up Web users for Web Remote Management In iTM integrator only managers are permitted The maximum number of managers that can be registered is 4 3 Passwords button...

Page 284: ...o be used in the iTM integrator The unit of temperature follows the locale of the accessed iTM unit NOTE 9 Backup button Exports the iTM integrator backup data to USB memory 10 Version Info button Dis...

Page 285: ...ot simultaneously open the same setup screen History function The history displayed from the Operation Mgmt tab of the iTM integrator Menu List screen is the history of the iTM integrator unit can sav...

Page 286: ...ata you can import export are as follows Setup export History Power proportional distribution data optional Energy Navigator data optional The output files are named in a similar way as when output by...

Page 287: ...If a setup screen is open the settings in progress are canceled Area member registration When the OK button is pressed on the Registration screen Area attributes change When the OK button is pressed...

Page 288: ...sed on the deletion confirmation dialog Controller name System settings changed Please access again Area member registration When the OK button is pressed on the Registration screen Area attributes ch...

Page 289: ...ntenance 13 1 Resetting the Filter Sign Reset filter sign after cleaning the air conditioner with the sign ON 1 2 1 Select 1 with the filter sign ON on the Standard View screen and touch the Setting b...

Page 290: ...play When the surface of the LCD of the iTM or the iTM unit is dirty wipe the dirt off with a piece of soft cloth soaked in a diluted neutral detergent and wrung sufficiently Do not use strongly acid...

Page 291: ...cklight Auto is set to OFF Backlight Auto Off is a function that automatically turns the display OFF when the screen is left untouched for a certain period of time The display does not go out automati...

Page 292: ...3 seconds to reflect the air conditioners current status The screen flickers each time it is refreshed but this is normal The operation performed by touching the iTM screen takes some time to be refl...

Page 293: ...able Furthermore when there are two iTMs connected R C Prohibition and Setpoint Restriction are unavailable for the iTM set as sub Air conditioners cannot be started or stopped as the iTM went out of...

Page 294: ...tralized monitoring screen Measure Operation commands cannot be sent to equipment in an emergency stop state Cause 3 A power failure occurred Checking method Use the iTM s Schedule function to check i...

Page 295: ...r Change the name of the file contained in the USB memory Delete the file contained in the USB memory Confirm that deleting the file does not cause a problem The USB memory is not connected to iTM Con...

Page 296: ...ed by schedule In the case above Interlocking Control stops 1 01 though it was started by Schedule It looks as if it is not working When setting up a schedule or interlocking control carefully conside...

Page 297: ...r details of remote controller operation settings see 2 6 Enabling Disabling Remote Controller An area or indoor unit cannot be operated from the Standard View screen Check the Standard View screen fo...

Page 298: ...ation of Chiller management points Cautions when monitoring setting up a Chiller A Chiller management point can read and write the specific objects on a MicroTech III controller POL687 70 MCQ which is...

Page 299: ...embedded in an AHU via BACnet IP connection On that basis the total operation of an AHU from intelligent Touch Manager should be ensured by mechanical the installers and control engineering firms Abou...

Page 300: ...tate because it cannot be distributed to any other air conditioner when it is set up not to distribute the power This total power needs to be separately handled as common utility expenses etc To displ...

Page 301: ...ile is corrupt or the file is invalid due to a filename change etc Save the data again from the iTM to a USB memory and start the CSV output tool Invalid data message If the File Output Error message...

Page 302: ...leaving the controller turned OFF for a long time 6 months or more set the BACKUP switch to OFF Setting this switch to OFF does not erase area management point settings schedules etc If power is not...

Page 303: ...nd displaying a balloon If set up the buzzer will also sound Red Flashing System error Text System error occurred Touch this icon to check and restore Yellow Flashing Unit Limit Error Text Error occur...

Page 304: ...The time the error occurred Name The name of the management point system where the error occurred Contents The content of the error Error Code The error code Contact an authorized dealer registered i...

Page 305: ...1 iTM Hardware Specifications 243mm 207mm 290mm 256 6mm Power AC100 240V 50 60Hz Power consumption 23 W Emergency stop input Always a contact Contact current approximately 10 mA Size 290 243 50 W H D...

Page 306: ...3 Copyright and Trademarks SDHC Logo is a trademark of SD 3C LLC The real time OS eT Kernel the network protocol PrCONNECT Pro the file system PrFILE2 and the USB stack PrUSB installed on this produc...

Page 307: ...Dio management point D3Chiller management point Up to 320 Outdoor unit and Inv Chiller management point Up to 56 External management point Up to 512 Total of External management point BACnet managemen...

Page 308: ...p to 650 Number of management points that can be used in an emergency stop signal Up to 6 Auto Changeover function Number of groups that can be created Up to 512 groups Number of management points tha...

Page 309: ...January to December Actual energy consumption registration Conversion factor of 0 to 9999 999 can be entered Number of Energy Groups Up to 30 groups Number of Pi management points that can be registe...

Page 310: ...to 1 From E mail addresses System functions System Settings function Passwords Administrator password 1 to 15 characters Screen unlock password 1 to 15 characters Management point area settings See Ce...

Page 311: ...rmats Three patterns available DD MM YYYY MM DD YYYY YYYY MM DD Decimal point CSV separator or Unit of temperature Temperature symbol C F Icon color Icon color Red green Hardware Luminance 8 levels be...

Page 312: ...ease the temperature settings by 4 C Schedule setup Interrock setup only Decrease the temperature settings by 3 C Decrease the temperature settings by 2 C Decrease the temperature settings by 1 C Incr...

Page 313: ...Reheat Start Stop Low Noise On Off Storage Water Setpoint Celsius Example 32 C Fahrenheit Example 90 F 1 Not displayed when Setback Control is disabled 2 Not displayed when Operation Mode Dry is disab...

Page 314: ...10 7 8 17 7 8 10 Increase the temperature settings by 3 C 7 8 10 7 8 17 7 8 10 Increase the temperature settings by 4 C 7 8 10 7 8 17 7 8 10 Fahrenheit Decrease the temperature settings by 7 F 7 8 10...

Page 315: ...Setup for centralized monitoring Disable Interval 1 2 3 4 5 6 7 8 9 10 Analog Example 0 00 MultiState Example Cool Heat Recovery Ao Mo tab Analog Example 0 00 6 9999 99 9999 99 w o unit MultiState Ex...

Page 316: ...e temperature settings by 1 C 7 8 7 8 13 7 8 Increase the temperature settings by 2 C 7 8 7 8 13 7 8 Increase the temperature settings by 3 C 7 8 7 8 13 7 8 Increase the temperature settings by 4 C 7...

Page 317: ...ab Repeat Mode Enable Disable Enable Only Detailed Setup for centralized monitoring Disable Interval 1 2 3 4 5 6 7 8 9 10 Analog Example 0 00 MultiState Example Cool Heat Recovery Ao Mo tab Analog Exa...

Page 318: ...ure Celsius Example 0 0 C 1 2 4 512 0 512 0 Step 0 1 Fahrenheit Example 32 F 1 2 4 890 954 Step 1 Generic Example 0 00 1 4 9999 99 9999 99 Step 0 01 Example Room Temp1 3 Mgmt Point Offset Temperature...

Page 319: ...rd Screen unlock function is only available in iTM Screensaver Setup only available in iTM Hardware Setup only available in iTM Touch Panel Calibration Setup only available in iTM Time DST Setup Regio...

Page 320: ...ed in a single line The area information identifier is described as the single byte character A while the management point information identifier is described as a single byte character P The number o...

Page 321: ...of area configuration and CSV file format 1 2 3 8 4 5 6 7 9 10 11 12 13 1F North 1F South Meeting Room Aisle Room A Room B Indoor A Indoor B Of ce Indoor Ventilator 1 Lavatory Building A TOP ALL Indo...

Page 322: ...ejected by SMTP server E mail Address Mail ID E mail ID E mail Error A071 SMTP user authentication failed E mail Address Mail ID E mail ID E mail Error A072 Other authentication method is required E m...

Page 323: ...detected 3 Management Point Name Release B032 Communication restored Management Point Name Status Change Status B101 Start Stop Setback High Setback Low Management Point Name Status Source 4 Status B...

Page 324: ...ume Energy Saving Control Energy Save Setup Source Auto Ctrl Higher level Central Control Control C101 Central Control is enabled DIII NET Control C102 Central Control is disabled DIII NET Setback Set...

Page 325: ...sed the status change Status Source When the Status Source is Web the User Name is also added When the Status Source is other than control equipment other than iTM the Instructed by information is not...

Page 326: ...TM Version iTM version Program Name Program name Enable Disable Program enabled disabled Enable Disable Period Validity period of the program All is output when the Schedule is enabled for all term Su...

Page 327: ...Special day 5 Time P A Name Action Special Day Name of the Special day 1 Date or Month Day of the week setting of Special day 1 Month day Name of the Special day 2 Date or Month Day of the week settin...

Page 328: ...uch Manager 327 A B C D Calendar Preview Week Date 1 2 3 Year Month Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Ditto Blank Program Name The settings of the second or subsequent...

Page 329: ...Ditto Ditto Output 1 Detection Conditions Input condition for interlocked output Start Stop Interval sec Sequential start stop interval P A Name Action Area Mgmt Point Area Management point name Manag...

Page 330: ...ogram enabled disabled Enable Disable Input Release Mode Release mode Automatic Manual Mgmt Point Input signal s management point name Ditto Output Specification method Output method Listed Points Unl...

Page 331: ...ed in the group Ditto Blank Group Name Group name Enable Disable The settings of the second or subsequent program will be output following above Temperature Limit CSV file format Shadowed data are fix...

Page 332: ...emperature Range Outdoor temperature range Upper limit Lower limit Setpoint Range Setpoint range Upper limit Lower limit Mgmt Point Name of management point included in the group Ditto Blank Group Nam...

Page 333: ...able Enable Disable Set up excluded time Mon Ditto Ditto Tue Ditto Ditto Wed Ditto Ditto Thu Ditto Ditto Fri Ditto Ditto Sat Ditto Ditto Exceptions to Excluded Time Normal Exceptions to Excluded Time...

Page 334: ...me Export Date Output date iTM Version iTM version Cool Recovery Temp Cool Recovery Temp Heat Recovery Temp Heat Recovery Temp High Relative Setup Setpoint Setback High Relative Setup Setpoint High Re...

Page 335: ...Time Note 1 00 01 04 2012 0 0 0 ID Unit 512 standby power ID Unit 1 standby power 3 00 2 00 ID Unit 512 power ID Unit 1 power ID Unit 512 standby power ID Unit 512 power ID Unit 2 standby power ID Un...

Page 336: ...low the System Settings iTM Version iTM version Data period Data period Data target Name Example All 1F Mgmt pnt Area Area Mgmt pnt Example Mgmt pnt Blank Administering Rules Name Administering Rules...

Page 337: ...ata period Data period Data target Name Example All 1F Mgmt pnt Area Area Mgmt pnt Example Mgmt pnt Blank Administering Rules Name Administering Rules Name Month Day Special Day Pattern Jan 3rd Wed Sp...

Page 338: ...displayed when data is of the past or there are no planned values Month Data collection start month Example 1 Data collection end month Example 12 Actual energy consumption kWh m3 Planned energy consu...

Page 339: ...31 Actual energy consumption New Conversion Type Unit 1000 1500 Day 1 End of the month Example 31 Management point name 1 kWh m3 Displays only management point registered with an Energy Group and matc...

Page 340: ...net Di BACnet Dio Analog Ai External Ai Internal Ai BACnet Ai Pulse Pi External Pi Internal Pi A B C D Blank Controller Name Controller name Export Date Output date The format for date and time follow...

Page 341: ...lue 248 6 Suction Temperature Minimum Value Minimum 1 minute value in 1 hour data collection time C F 50 0 Value 120 0 58 Value 248 7 Operation time of cooling Total Accumulated indoor unit s operatio...

Page 342: ...tion time C F 50 0 Value 120 0 58 Value 248 7 Outlet Water Temp Average 15 minute average of 1 minute data over 1 hour data collection time C F 50 0 Value 120 0 58 Value 248 8 Outlet Water Temp Maximu...

Page 343: ......

Page 344: ...EM11A015B 1409 HT...

Reviews: