User’s Manual EM11A015B
intelligent Touch Manager
264
Cautions when Using Simultaneously with Other Control Functions
1.
Automatic control functions that work when there is no one in the room (such as Setback,
Temperature Limit, Pre-Cool/Pre-Heat) are exempt from the operation rules during their
operating hours.
2.
Automatic control functions that work when there are people in the room (Auto Changeover,
HMO, Timer Extension, Sliding Temperature, Schedule, Interlocking Control) are subject to the
operation rules during their operating hours.
3.
The operation rules do not apply to management points under maintenance or leakage check.