![background image](http://html1.mh-extra.com/html/daikin/dcm601a51/dcm601a51_user-manual_3232430157.webp)
User’s Manual EM11A015B
intelligent Touch Manager
156
3.
Effect on Other Functions
Use of Switch as trigger
Use of On/Off status for assessment
Central Monitoring
−
•
Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Treated as OFF
Automatic
Control
Schedule
−
−
Pre-Cool/Pre-
Heat
−
−
Interlocking
•
Start order by Setback
⇒
Treated as start trigger
• Stop order by Setback
⇒
Treated as stop trigger
−
Emergency
Stop
−
−
Auto
Changeover
−
•
Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Temperature
Limit
−
•
Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Not treated as OFF
Sliding
Temperature
−
−
HMO
−
•
Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Timer
Extension
•
Start order by Setback
⇒
Not treated as start trigger
• Stop order by Setback
⇒
Treated as stop trigger
•
Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Data
Management
Power
Proportional
Distribution
−
•
Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Treated as OFF
Energy
Navigator
(Timer
Extension
sampling)
−
•
Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Operation
time trend
−
•
Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Treated as OFF
Start/Stop
count trend
•
Start order by Setback
⇒
Treated as start trigger
• Stop order by Setback
⇒
Treated as stop trigger
−