[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
BS_07_M
chapter 7 -
11
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-3
Error Code Definitions and Solutions: Codes [1000 - 1999]
7-3-1
Error Code [1102]
1. Error code definition
Discharge temperature fault
2. Error definition and error detection method
1) If the discharge temperature of 120 °C [248°F] or more is detected during the operation (the first detection), the outdoor unit
stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the discharge temperature of 120° C [248°F] or more is detected again (the second detection) within 30 minutes after the
second stop of the outdoor unit described above, the mode will be changed to 3 - minute restart mode, then the outdoor unit
will restart in 3 minutes.
3) If the discharge temperature of 120°C [248°F] or more is detected (the third detection) within 30 minutes after the stop of the
outdoor unit described above (regardless of the first or the second stop), the outdoor unit will make an error stop, and the error
code "1102" will be displayed.
4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor
unit, the detection is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the
LED display.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Gas leak, gas shortage
Refer to the following page(s). [6-3 Evaluating and Adjusting
Refrigerant Charge]
(2)
Overload operation
Check operating conditions and operation status of indoor/
outdoor units.
(3)
HBC LEV malfunction
Cooling only: LEV1, 2, and 3
Cooling main: LEV1, 2, and 3
Heating only or heating main: LEV1, 2, and 3
Defrost: LEV1, 2, and 3
Perform a heating operation and check the operation.
Cooling: HBC LEV1, 2, and 3
SV1
21S4Ma and 21S4Mb
Heating: HBC LEV1, 2, and 3
SV1
21S4Ma and 21S4Mb
Refer to the following page(s). [8-8 Troubleshooting LEV,
FCV Problems]
(4)
HBC SV1, 21S4Ma, and 21S4Mb malfunc-
tion
→
Cooling only or defrost
(5)
HBC SV1, 21S4Ma, and 21S4Mb malfunc-
tion
→
Cooling only or cooling main
(6)
HBC SV1, 21S4Ma, and 21S4Mb malfunc-
tion
→
Heating only or heating main
(7)
Actuation failure in the four-way valve (21S4a
or 21S4b) or the expansion valve (LEV2a or
LEV2b)
→
heating only, heating main
(8)
Port address setting error.
Confirm the port address of the indoor unit.
(9)
Refrigerant service valve actuation failure
Confirm that the refrigerant service valve is fully open.
(10)
Outdoor fan (including fan parts) failure, mo-
tor failure, or fan controller malfunction
Rise in discharge temp. by low pressure
drawing for (3) - (11).
Check the fan on the outdoor unit.
Refer to the following page(s). [8-7 Troubleshooting Outdoor
Unit Fan Problems]
(11)
Gas leak between low and high pressures
(4-way valve failure, Compressor failure, So-
lenoid valve (SV1a) failure)
Perform a cooling or heating operation and check the opera-
tion.
(12)
Thermistor failure
(TH4)
Refer to the following page(s). [7-7-3 Error Code
[5103,5104,5105,5107,5115]]
(13)
Input circuit failure on the controller board
thermistor
Check the inlet air temperature on the LED monitor.
(14)
Outdoor unit LEV4 valve actuation failure
Refer to the following page(s). [8-8 Troubleshooting LEV,
FCV Problems]
0000006452.BOOK 11 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......