[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
BS_07_M
chapter 7 -
35
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-14
Error Code [4220, 4225, 4226] Detail Code 108
1. Error code definition
Abnormal bus voltage drop (Detail code 108)
2. Error definition and error detection method
[Outdoor unit]
If Vdc 289V or less is detected during Inverter operation. (S/W detection)
[HBC]
If Vdc 150V or less is detected during Inverter operation. (S/W detection)
3. Cause, check method and remedy
[Outdoor unit]
(1) Power supply environment
Check the power-supply wiring for an open phase. Refer to item (6) in section [6-1 Read before Test Run].
Find out if there was a (momentary) power failure.
Check whether the power voltage (Between L1 and L2, L2 and L3, and L1 and L3) is 342V or less across all phases.
(2) Voltage drop detected
4220
INV35Y, INV42Y, and INV37YC
Check the voltage at relay connector RYPN while the inverter is stopped.
If the voltage is 420 V or above, check the following items.
1) Check the LED monitor to see if the bus voltage is above 289 V, and replace the inverter board if it is 289 V or below.
2) Check the coil (L) connections and for broken wiring.
3) Check the wiring connections between noise filter board and INV board.
4) If the problem persists after reboot, replace the INV board.
If the voltage is below 420 V, check the following items.
1) Check the coil (L) connections and for broken wiring.
2) Check the wiring connections between noise filter board and INV board and between INV board and R1 through R5.
3) Check the in-rush current resistor. Refer to the following page(s). [8-10-18 Simple Check on Inverter Circuit Compo-
nents]
4) If the problem persists after reboot, replace the INV board.
4225, 4226
Check the voltage at relay connector RYPN while the inverter is stopped. If the voltage is below 420 V, check the following
items.
1) Check for proper connections of noise filter coil and DC reactor, and for broken wiring.
2) Check the wiring connections between INV board and FAN board.
3) Check item for 4220
Replace the FAN board if no problems are found.
Check the voltage at connector RYPN while the inverter is stopped. If the voltage is 420 V or above, check the following items.
1) Check the state of the wiring connections between the INV board and the Fan board.
2) Check contents 4220
Replace the Fan board if no problems are found.
(3) Control board failure
Check that 12VDC is applied to connector CN72 on the control board while the inverter is operating. If voltage is absent or
the wrong voltage is applied, check the fuse F01. Replace the control board if no problems are found with the fuse.
0000006452.BOOK 35 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......