vi
Use the following tools specifically de-
signed for use with the specified refriger-
ant: Gauge manifold, charge hose, gas leak
detector, check valve, refrigerant charge
base, vacuum gauge, and refrigerant recov-
ery equipment.
Gas leak detectors for conventional refrigerants will not
react to a refrigerant that does not contain chlorine.
If the specified refrigerant is mixed with water, refriger-
ant oil, or another refrigerant, the refrigerant oil will de-
teriorate and the compressor will malfunction.
Use a vacuum pump with a check valve.
If the vacuum pump oil flows back into the refrigerant
lines, the refrigerant oil may deteriorate and the com-
pressor may malfunction.
Keep tools clean.
If dust, dirt, or water accumulates on the charging hose
or the flare processing tool, the refrigerant will deterio-
rate and the compressor will malfunction.
Use refrigerant piping made of phosphorus
deoxidized copper (copper and copper alloy
seamless pipes) that meets local require-
ments. Pipe joints should also meet local re-
quirements. Keep the inner and outer
surfaces of the pipes clean and free of sul-
phur, oxides, dust/dirt, shaving particles,
oils, moisture, or any other contaminants.
Contaminants on the inside of the refrigerant piping will
cause the refrigerant oil to deteriorate and cause the
compressor to malfunction.
Store pipes indoors, and keep both ends of
the pipes sealed until just before making a
flare connection or brazing. (Store elbows
and other joints in plastic bags.)
If dust, dirt, or water enters the refrigerant lines, the re-
frigerant oil will deteriorate and the compressor will
malfunction.
Braze the pipes with a nitrogen purge to
avoid oxidation.
Oxidized flux inside the refrigerant pipes will cause the
refrigerant oil to deteriorate and cause the compressor
to malfunction.
Do not use existing refrigerant piping.
The old refrigerant and refrigerant oil in the existing pip-
ing contain a large amount of chlorine, which will cause
the refrigerant oil in the new unit to deteriorate and
cause the compressor to malfunction.
If a large electric current flows due to a mal-
function or faulty wiring, earth-leakage
breakers on the unit side and on the up-
stream side of the power supply system
could both operate. Depending on the im-
portance of the system, separate the power
supply system or take protective coordina-
tion of breakers.
This appliance is intended to be used by ex-
pert or trained users in shops, in light indus-
try and on farms, or for commercial use by
lay persons.
This appliance is not intended for use by
persons (including children) with reduced
physical, sensory or mental capabilities, or
lack of experience and knowledge, unless
they have been given supervision or in-
struction concerning use of the appliance
by a person responsible for their safety.
Store the unit in a room large enough to al-
low clearance in the event of refrigerant
leakage.
Refrigerant R32 is flammable. Do not use a
naked-flame type detector.
Only qualified personnel may touch the
USB port in the control box.
0000002721.BOOK vi ページ 2021年10月7日 木曜日 午後4時53分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......