[8-10 Troubleshooting Inverter Problems ]
BS_08_L
chapter 8 -
41
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
Error display/failure condition
Measure/inspection item
[1]
Inverter related errors
4250, 4255, 4256, 4220, 4225, 4226, 4230, 4240, 4260, 5301,
5305, 5306, 0403
Implement solutions that correspond to the error codes or preliminary
error codes. [7-1 Error Code and Preliminary Error Code Lists]
[2]
Main power breaker trip
Refer to the following page(s). [8-10-16 Solutions for the Main Breaker
Trip]
[3]
Main power earth leakage breaker trip
Refer to the following page(s).
[8-10-17 Solutions for the Main Earth Leakage Breaker Trip]
[4]
Only the compressor does not operate.
Check the inverter frequency on the LED monitor. If the frequency indi-
cates that the units are in operation, refer to the following page(s).
[8-10-5 Checking the Inverter for Damage during Compressor Opera-
tion]
[5]
The compressor vibrates violently at all times or makes an abnor-
mal sound.
Refer to the following page(s).
[8-10-5 Checking the Inverter for Damage during Compressor Opera-
tion]
[6]
Compressor rotation speed does not reach the specified speed.
<1> Check for problems with compressor current and heatsink tem-
perature.
<2> Check for imbalance in power supply voltage. *Approximate target:
3% or less.
[7]
Only the fan motor does not operate.
Check the inverter frequency on the LED monitor. If the frequency indi-
cates that the units are in operation, refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-10-9 Checking the Fan Board for Damage at No Load]
[8-10-10 Checking the Fan Board for Damage with Load]
[8]
The fan motor shakes violently at all times or makes an abnormal
sound.
Check the inverter frequency on the LED monitor. If the frequency indi-
cates that the units are in operation, refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-10-9 Checking the Fan Board for Damage at No Load]
[8-10-10 Checking the Fan Board for Damage with Load]
[9]
Only the pump of the HBC does not operate.
Refer to the following pages if the HBC is operating.
[8-10-12 Checking the Error-Detection Circuit on the Pump INV Board
(Without load)]
[8-10-13 Checking the Pump INV Board for Damage (Without load)]
[8-10-14 Checking the Pump INV Board for Damage (During pump op-
eration)]
[10]
Only the pump of the HBC constantly vibrates heavily or makes ab-
normal sounds.
[11]
Noise is picked up by the peripheral device.
<1> Check that power supply wiring of the peripheral device does not
run close to the power supply wiring of the outdoor unit.
<2> Check if the inverter output wiring is not running parallel to the
power supply wiring and the transmission lines.
<3> Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<4> Meg failure for electrical system other than the inverter
<5> Attach a ferrite core to the inverter output wiring. (Contact the fac-
tory for details of the service part settings.)
<6> Provide separate power supply to the air conditioner and other
electric appliances.
<7> If the problem suddenly appeared, inverter output may have had a
ground fault. For details, refer to the following page(s).
[8-10-5 Checking the Inverter for Damage during Compressor Op-
eration]
*Contact the factory for cases other than those listed above.
[12]
Sudden malfunction (as a result of external noise)
<1> Check that the grounding work is performed properly.
<2>Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<3>Check that neither the transmission line nor the external connec-
tion wiring does not run close to another power supply system or
does not run through the same conduit pipe.
* Contact the factory for cases other than those listed above.
0000006416.BOOK 41 ページ 2021年10月26日 火曜日 午後5時30分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......