background image

50PG08---14

Single Package Rooftop Units

Electric Cooling with PURON

R

(R---410A) Refrigerant

and

COMFORT

Link

t

Controls

Installation Instructions

IMPORTANT

: This installation instruction contains basic unit

installation information including installation of field control
devices. For information on unit start-up, service, and operation,
refer to the unit Controls, Start-Up, Operation, Service, and
Troubleshooting Instructions also enclosed in the unit literature
packet.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1 -- Provide Unit Support

1

. . . . . . . . . . . . . . . . . . . . . . . . .

Step 2 -- Rig and Place Unit

4

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 3 -- Field Fabricate Ductwork

6

. . . . . . . . . . . . . . . . . . . . . .

Step 4 -- Make Unit Duct Connections

6

. . . . . . . . . . . . . . . . . . .

Step 5 -- Install External Trap for Condensate Drain

6

. . . . . . . .

Step 6 -- Make Electrical Connections

7

. . . . . . . . . . . . . . . . . . .

Step 7 -- Install Outdoor--Air Hoods

(Units With Economizer)

19

. . . . . . . . . . . . . . . . . . . . .

Step 8 -- Install All Accessories

19

. . . . . . . . . . . . . . . . . . . . . . .

Step 9 -- Configuring Controls

19

. . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be

hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or

service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions
of replacing filters. All other operations should be performed by

trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags and labels

attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use

quenching cloth for unbrazing operations. Have fire extinguishers

available for all brazing operations.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the furnace and in instructions or

manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and

CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies a hazard

which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight
suggestions which

will

result in enhanced installation, reliability, or

operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal

injury or death.
Before performing service or maintenance operations

on unit, turn off main power switch to unit and install

lockout tag. Ensure electrical service to rooftop unit

agrees with voltage and amperage listed on the unit

rating plate.

!

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personal

injury, death and/or equipment damage.
Puron (R--410a) refrigerant systems operate at higher

pressures than standard R--22 systems. Do not use R--22

service equipment or components on Puron refrigerant

equipment.

!

WARNING

IMPORTANT

: Units have high ambient operating limits. If limits

are exceeded, the units will automatically lock the compressor out
of operation. Manual reset will be required to restart the
compressor.

INSTALLATION

Step 1 — Provide Unit Support

Roof Curb

Assemble or install accessory roof curb in accordance with

instructions shipped with this accessory. (See Fig. 1.) Install
insulation, cant strips, roofing, and counter flashing as shown.

Ductwork can be installed to roof curb before unit is set in place.
Ductwork must be attached to curb and not to the unit. Curb must

be level. This is necessary to permit unit drain to function properly.

Unit leveling tolerance is

±

1

/

16--

in. per linear ft in any direction.

Refer to Accessory Roof Curb Installation Instructions for

additional information as required. When accessory roof curb is
used, unit may be installed on class A, B, or C roof covering

material. Carrier roof curb accessories are for flat roofs or slab

mounting.

Summary of Contents for 50PG08 14 Series

Page 1: ...AUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result...

Page 2: ...2 C06252 Fig 1 Roof Curb Dimensions 50PG08 14 ...

Page 3: ...3 C06313 Fig 2 Base Unit Dimensions 50PG08 14 ...

Page 4: ...After unit is in position remove top crating and polyethylene sheet Roof Mount Check building codes for weight distribution requirements Unit operating weight is shown in Table 1 Installation Onto Curb The 50PG units are designed to fit on the accessory full perimeter curb In either case correct placement of the unit onto the curb is critical to operating performance To aid in correct positioning ...

Page 5: ...y Fins Face Split Rows Fins in 3 15 3 15 4 15 4 15 Face Area sq ft 14 9 14 9 14 9 14 9 EVAPORATOR FAN Centrifugal Type Belt Drive Quantity Size in Low 1 15 x 15 1 15 x 15 1 15 x 15 1 15 x 15 High 1 15 x 15 1 15 x 15 1 15 x 15 1 15 x 15 Type Drive Low Belt Belt Belt Belt High Belt Belt Belt Belt Nominal Cfm 3000 3400 4000 5000 Maximum Continuous Bhp Low 2 40 2 40 3 10 3 70 High 3 10 3 70 3 70 5 25 ...

Page 6: ...uctwork to unit do not drill in area below bead or above top edge of duct opening Step 5 Install External Trap for Condensate Drain The unit s 3 4 in condensate drain connections are located on the bottom and side of the unit If the down drain is used drill a minimum of a 5 8 in diameter hole but not larger than a 3 4 in diameter hole through the drain pan A dimple of 2 mm in diameter and 1 5 mm d...

Page 7: ...on and moving to the 200 v 1 4 in male terminal on the primary side of the transformer Refer to unit label diagram for additional information Leads are provided for field wire connections Use UL Underwriters Laboratories approved copper aluminum connector When installing units provide safety disconnect per NEC National Electrical Code Article 440 or local codes For non fused disconnects size the d...

Page 8: ... a Carrier approved accessory thermostat or a Carrier approved space temperature sensor Install thermostat according to the installation instructions included with accessory Locate thermostat assembly or space temperature sensor on a solid interior wall in the conditioned space to sense average temperature Route thermostat or space temperature sensor cable or equivalent single leads of colored wir...

Page 9: ...ge humidity Carrier Thermidistat device wiring connections are shown in Fig 11 General humidistat wiring connections are shown in Fig 12 Configuration of the unit control is required to specify the control input type before unit operation Refer to the Controls Start up Operation and Troubleshooting manual for configuration Units with the Humidi MiZer option receive a discrete input from a field in...

Page 10: ...10 C07191 Fig 13 Third Party Smoke Detector on Humidi MiZert 50PG08 14 ...

Page 11: ... 70 57 110 1 2 Low 2 6 19 8 20 21 100 11 5 10 0 19 8 20 21 100 17 3 15 0 26 4 30 24 100 28 9 25 0 40 9 45 38 100 40 4 35 0 55 3 60 51 100 46 2 40 0 62 5 70 58 100 High 3 4 20 6 25 22 113 11 5 10 0 20 6 25 22 113 17 3 15 0 27 4 30 25 113 28 9 25 0 41 9 45 39 113 40 4 35 0 56 3 60 52 113 46 2 40 0 63 5 70 58 113 LEGEND FLA Full Load Amps HACR Heating Air Conditioning and Refrigeration IFM Indoor Eva...

Page 12: ... 2 50 50 50 50 222 222 30 0 34 6 11 3 15 0 47 8 53 5 50 60 50 50 222 222 50 0 57 7 18 8 25 0 72 8 82 4 80 90 67 76 222 222 70 0 80 8 26 3 35 0 97 8 111 3 100 125 90 102 222 222 80 0 92 4 30 0 40 0 110 3 125 8 125 150 101 116 222 222 High 10 2 52 2 52 2 60 60 55 55 265 265 20 0 23 1 7 5 10 0 52 2 52 2 60 60 55 55 265 265 30 0 34 6 11 3 15 0 54 0 59 8 60 60 55 55 265 265 50 0 57 7 18 8 25 0 79 0 88 ...

Page 13: ...5 11 5 10 0 23 9 25 25 135 17 3 15 0 27 4 30 25 135 28 9 25 0 41 9 45 39 135 40 4 35 0 56 3 60 52 135 46 2 40 0 63 5 70 58 135 57 7 50 0 63 5 70 72 135 High 4 8 25 3 30 27 144 11 5 10 0 25 3 30 27 144 17 3 15 0 29 1 30 27 144 28 9 25 0 43 6 45 40 144 40 4 35 0 58 0 60 53 144 46 2 40 0 65 3 70 60 144 57 7 50 0 65 2 70 73 144 575 3 60 518 633 6 1 40 2 0 8 Low 2 8 18 1 20 19 106 13 9 15 0 20 9 25 19 ...

Page 14: ...8 6 45 1 60 0 166 6 155 1 175 175 153 175 383 383 High 15 0 72 2 72 2 80 80 77 77 392 392 20 0 23 1 7 5 10 0 72 2 72 2 80 80 77 77 392 392 30 0 34 6 11 3 15 0 72 2 72 2 80 80 77 77 392 392 50 0 57 7 18 8 25 0 85 0 94 6 90 100 78 87 392 392 70 0 80 8 26 3 35 0 110 0 123 5 125 125 101 114 392 392 100 1 115 5 37 6 50 0 147 6 138 0 150 150 136 154 392 392 120 1 138 6 45 1 60 0 172 6 161 1 175 175 159 ...

Page 15: ... 8 70 60 112 1 2 Low 2 6 22 0 25 23 102 11 5 10 0 22 0 25 23 102 17 3 15 0 29 1 30 27 102 28 9 25 0 43 6 45 40 102 40 4 35 0 58 0 60 53 102 46 2 40 0 65 3 70 60 102 High 3 4 22 8 25 24 115 11 5 10 0 22 9 25 24 115 17 3 15 0 30 1 35 28 115 28 9 25 0 44 6 45 41 115 40 4 35 0 59 0 60 54 115 46 2 40 0 66 3 70 61 115 LEGEND FLA Full Load Amps HACR Heating Air Conditioning and Refrigeration IFM Indoor E...

Page 16: ...2 0 60 60 55 55 227 227 30 0 34 6 11 3 15 0 53 8 59 5 60 60 55 55 227 227 50 0 57 7 18 8 25 0 78 8 88 4 80 90 72 81 227 227 70 0 80 8 26 3 35 0 103 8 117 3 110 125 95 108 227 227 80 0 92 4 30 0 40 0 116 3 131 8 125 150 107 121 227 227 High 10 2 57 0 57 0 60 60 61 61 270 270 20 0 23 1 7 5 10 0 57 0 57 0 60 60 61 61 270 270 30 0 34 6 11 3 15 0 60 0 65 8 70 70 61 61 270 270 50 0 57 7 18 8 25 0 85 0 9...

Page 17: ...37 11 5 10 0 26 1 30 28 137 17 3 15 0 30 1 35 28 137 28 9 25 0 44 6 45 41 137 40 4 35 0 59 0 60 54 137 46 2 40 0 66 3 70 61 137 57 7 50 0 66 2 70 74 137 High 4 8 27 5 30 29 146 11 5 10 0 27 5 30 29 146 17 3 15 0 31 9 35 29 146 28 9 25 0 46 4 50 43 146 40 4 35 0 60 8 70 56 146 46 2 40 0 68 0 70 63 146 57 7 50 0 68 0 70 76 146 575 3 60 518 633 6 1 40 2 0 8 Low 2 8 19 8 20 21 108 13 9 15 0 23 0 25 21...

Page 18: ... 120 1 138 6 45 1 60 0 172 6 161 1 175 175 159 180 388 388 High 15 0 77 0 77 0 80 80 82 82 397 397 20 0 23 1 7 5 10 0 77 0 77 0 80 80 82 82 397 397 30 0 34 6 11 3 15 0 77 0 77 0 80 80 82 82 397 397 50 0 57 7 18 8 25 0 91 0 100 6 100 110 84 93 397 397 70 0 80 8 26 3 35 0 116 0 129 5 125 150 107 119 397 397 100 1 115 5 37 6 50 0 153 6 144 0 175 150 141 159 397 397 120 1 138 6 45 1 60 0 178 6 167 1 2...

Page 19: ... HOOD ECONOMIZER PANEL POWER EXHAUST C06260 Fig 15 Hood Installation 4 Hang the barometric relief power exhaust hood on the mounting flange on the economizer panel Secure hood to panel with screws saved from Step 2 See Fig 15 and 16 5 Align hole in flange of economizer panel with left edge of hood Hang economizer hood on the top flange of the economizer panel by rotating hood until top flange of t...

Page 20: ... Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 03 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50PG 41SI Replaces 50PG 37SI 50PG08 14 ...