17
Table 3 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER SUPPLY
Volts-Ph-Hz
VOLTAGE
RANGE
COMPRESSOR
(Each)
OFM
POWER
EXHAUST
FLA
IFM
TYPE
IFM
FLA
ELECTRIC HEAT
POWER SUPPLY
DISCONNECT
SIZE
Min
Max
RLA
LRA
Qty FLA
FLA
Nominal
kW*
MCA
MOCP†
FLA
LRA
12
208/230-3-60
187
253
17.6
123
2
1.9
—
Low
7.5
—
—
55.7/ 55.7
60/ 60
59/ 59 315/315
20.0/ 23.1
7.5/10.0
55.7/ 55.7
60/ 60
59/ 59 315/315
30.0/ 34.6 11.3/15.0
55.7/ 58.6
60/ 60
59/ 59 315/315
50.0/ 57.7 18.8/25.0
77.9/ 87.5
80/ 90
72/ 81 315/315
70.0/ 80.8 26.3/35.0
102.9/116.4 110/125
95/107 315/315
80.0/ 92.4 30.0/40.0
115.4/130.9 125/150 106/120 315/315
100.1/115.5 37.6/50.0
140.5/130.9 150/150 129/147 315/315
High
10.2
—
—
58.4/ 58.4
60/ 60
62/ 62 332/332
20.0/ 23.1
7.5/10.0
58.4/ 58.4
60/ 60
62/ 62 332/332
30.0/ 34.6 11.3/15.0
58.4/ 62.0
60/ 70
62/ 62 332/332
50.0/ 57.7 18.8/25.0
81.3/ 90.9
90/100
75/ 84 332/332
70.0/ 80.8 26.3/35.0
106.3/119.8 110/125
98/110 332/332
80.0/ 92.4 30.0/40.0
118.8/134.3 125/150 109/124 332/332
100.1/115.5 37.6/50.0
143.9/134.3 150/150 132/150 332/332
3.0
Low
7.5
—
—
58.7/ 58.7
60/ 60
62/ 62 319/319
20.0/ 23.1
7.5/10.0
58.7/ 58.7
60/ 60
62/ 62 319/319
30.0/ 34.6 11.3/15.0
58.7/ 62.4
60/ 70
62/ 62 319/319
50.0/ 57.7 18.8/25.0
81.6/ 91.3
90/100
75/ 84 319/319
70.0/ 80.8 26.3/35.0
106.6/120.1 110/125
98/111 319/319
80.0/ 92.4 30.0/40.0
119.1/134.6 125/150 110/124 319/319
100.1/115.5 37.6/50.0
144.3/134.6 150/150 133/150 319/319
High
10.2
—
—
61.4/ 61.4
70/ 70
66/ 66 336/336
20.0/ 23.1
7.5/10.0
61.4/ 61.4
70/ 70
66/ 66 336/336
30.0/ 34.6 11.3/15.0
61.4/ 65.8
70/ 70
66/ 66 336/336
50.0/ 57.7 18.8/25.0
85.0/ 94.6
90/100
78/ 87 336/336
70.0/ 80.8 26.3/35.0
110.0/123.5 125/125 101/114 336/336
80.0/ 92.4 30.0/40.0
122.5/138.0 125/150 113/127 336/336
100.1/115.5 37.6/50.0
147.6/138.0 150/150 136/154 336/336
460-3-60
414
506
7.7
50
2
1.0
—
Low
3.4
—
—
24.9
25
26
134
11.5
10.0
24.9
25
26
134
17.3
15.0
28.6
30
26
134
28.9
25.0
43.1
45
40
134
40.4
35.0
57.5
60
53
134
46.2
40.0
64.8
70
60
134
57.7
50.0
64.7
70
73
134
High
4.8
—
—
26.3
30
28
143
11.5
10.0
26.3
30
28
143
17.3
15.0
30.4
35
28
143
28.9
25.0
44.9
45
41
143
40.4
35.0
59.3
60
55
143
46.2
40.0
66.5
70
61
143
57.7
50.0
66.5
70
74
143
1.2
Low
3.4
—
—
26.1
30
28
137
11.5
10.0
26.1
30
28
137
17.3
15.0
30.1
35
28
137
28.9
25.0
44.6
45
41
137
40.4
35.0
59.0
60
54
137
46.2
40.0
66.3
70
61
137
57.7
50.0
66.2
70
74
137
High
4.8
—
—
27.5
30
29
146
11.5
10.0
27.5
30
29
146
17.3
15.0
31.9
35
29
146
28.9
25.0
46.4
50
43
146
40.4
35.0
60.8
70
56
146
46.2
40.0
68.0
70
63
146
57.7
50.0
68.0
70
76
146
575-3-60
518
633
6.1
40
2
0.8
—
Low
2.8
—
—
19.8
20
21
108
13.9
15.0
23.0
25
21
108
23.1
25.0
34.5
35
32
108
32.3
35.0
46.0
50
42
108
37.0
40.0
51.9
60
48
108
46.2
50.0
51.8
60
58
108
High
—
—
19.8
20
21
108
13.9
15.0
23.0
25
21
108
23.1
25.0
34.5
35
32
108
32.3
35.0
46.0
50
42
108
37.0
40.0
51.9
60
48
108
46.2
50.0
51.8
60
58
108
LEGEND
FLA
--- Full Load Amps
HACR
--- Heating, Air Conditioning and Refrigeration
IFM
--- Indoor (Evaporator) Fan Motor
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
MOCP
--- Maximum Overcurrent Protection
NEC
--- National Electrical Code
OFM
--- Outdoor (Condenser) Fan Motor
RLA
--- Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
{
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%
. Use
the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230---3---60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage = 224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT
: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE031A00 are not required if field---supplied
pressure connectors are used. Factory---installed heaters contain terminal blocks when
combined MOCP is greater than 60 amps.
50PG08
--