[8-5 Pressure Sensor Circuit Configuration and Troubleshooting Pressure Sensor Problems ]
18
-
chapter 8
BS_08_L
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-5
Pressure Sensor Circuit Configuration and Troubleshooting
Pressure Sensor Problems
8-5-1
Comparing the High-Pressure Sensor Measurement and Gauge Pressure
Setting the digital display switch (SW4 (SW6-10: OFF) as follows will display the high-pressure sensor reading on the service
LED (LED301) on the control board.
(1) While the sensor is stopped, compare the gauge pressure and the pressure displayed on the
self-diagnosis service LED.
1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal pressure is caused due to gas leak.
2) When the pressure displayed on the self-diagnosis service LED is between 0 and 0.098MPa [14psi], the connector may be
defective or be disconnected. Check the connector and go to (4).
3) When the pressure displayed on the self-diagnosis service LED exceeds 4.15MPa [601psi], go to (3).
4) If other than 1), 2) or 3), compare the pressures while the sensor is running. Go to (2).
(2) Compare the gauge pressure and the pressure displayed on the self-diagnosis service LED
while the sensor is running. (Compare them by MPa [psi] unit.)
1) When the difference between both pressures is within 0.098MPa [14psi], both the high pressure sensor and the control board
are normal.
2) When the difference between both pressures exceeds 0.098MPa [14psi], the high pressure sensor has a problem. (perfor-
mance deterioration)
3) When the pressure displayed on the self-diagnosis service LED does not change, the high pressure sensor has a problem.
(3) Remove the high pressure sensor from the control board to check the pressure on the self-di-
agnosis service LED.
1) When the pressure displayed on the self-diagnosis service LED is between 0 and 0.098MPa [14psi], the high pressure sensor
has a problem.
2) When the pressure displayed on the self-diagnosis service LED is approximately 4.15MPa [601psi], the control board has a
problem.
(4) Remove the high pressure sensor from the control board, and short-circuit between the No.2
and 3 connectors (63HS1, PS1, PS3) to check the pressure with the self-diagnosis service LED.
1) When the pressure displayed on the self-diagnosis service LED exceeds 4.15MPa [601psi], the high pressure sensor has a
problem.
2) If other than 1), the control board has a problem.
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
0000006416.BOOK 18 ページ 2021年10月26日 火曜日 午後5時30分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......