[8-10 Troubleshooting Inverter Problems ]
BS_08_L
chapter 8 -
45
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-10-6
Checking the Converter for Damage during Compressor Operation
<INV37YC>
3)
An overcurrent error occurs during oper-
ation.
Error code : 4250
Detail code : 121,122
[8-10-6 Checking the Converter for
Damage during Compressor Oper-
ation]
4)
An overcurrent error occurs immediately
after compressor startup.
Error code : 4250
Detail code :101,106,107,128
a.
Check for refrigerant flooding.
→
When the problem persists after
compressor startup was repeated
several times, go to "d" after a cer-
tain time after energizing the com-
pressor or the heater.
If normal operation is restored,
check the belt heater for problems.
b.
Check that there is a pressure dif-
ference between high and low
pressures after compressor start-
up.
→
Check the high pressure with
LED monitor for changes.
Replace the compressor if there is
no pressure difference. (the com-
pressor may be locked.)
c.
Check for interphase voltage im-
balance.
d.
Replace the INV board if no prob-
lems were found with the items a or
c.
e.
If the problem persists after replac-
ing the inverter board, [8-10-3
Checking the Compressor for
Ground Fault and Coil Resistance
Problems]
5)
An overvoltage error occurs during oper-
ation.
Error code : 4220
Detail code :109,110,112
[8-10-6 Checking the Converter for
Damage during Compressor Oper-
ation]
6)
No problems were found with items 1)
through 5).
Normal [8-10-6 Checking the Con-
verter for Damage during Com-
pressor Operation]
Items to be checked
Phenomena
Remedy
Items to be checked
Phenomena
Remedy
(1)
Operate the outdoor unit.
1)
BUS voltage does not boost (does
not change) BUS voltage does not
boost to approximately between
650 and 750 VDC, or the following
errors are detected.
Error code : 4220
Detail code : 123
Replace the inverter board.
(2)
Check the BUS voltage after the
converter circuit went into oper-
ation and the BUS voltage has
boost.
*The voltage generally boost at
or above 80 rps, depending on
the power source voltage.
2)
An overcurrent error occurs after
converter circuit goes into opera-
tion.
Error code : 4250
Detail code : 121,122
a.If the problem persists after startup, re-
place the inverter board.
b.If the problem persists after replacing
the inverter board, replace the DCL.
3)
An overvoltage error occurs after
converter circuit goes into opera-
tion.
Error code : 4220
Detail code : 109,110,112
a.If the problem persists after startup, re-
place the inverter board.
b.If the problem persists after replacing
the inverter board, replace the DCL.
4)
No problems were found with items
1) through 3).
Normal
0000006416.BOOK 45 ページ 2021年10月26日 火曜日 午後5時30分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......