[7-4 Error Code Definitions and Solutions: Codes [2000 - 2999] ]
22
-
chapter 7
BS_07_M
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-4-9
Error Code [2519]
1. Error code definition
Water pressure drop
2. Error definition and error detection method
1) If the reading of the pressure sensor Pw1 or Pw2 is below 10 kPa while Pump 1 is in operation, or the reading of the pressure
sensor Pw3 or Pw4 is below 10 kPa while Pump 2 is in operation (first detection), the outdoor units and the pumps will stop,
go into the 3-minute restart delay mode, and then restart.
2) If the pressure reading goes down below 10 kPa again within 10 minutes of the stoppage of the pump and within 2 minutes
after the pump restarted (second detection), the outdoor units and the pumps will stop again, go into the 3-minute restart delay
mode, and then restart.
3) If the pressure reading goes down below 10 kPa again within 10 minutes of the stoppage of the pump and within 2 minutes
after the pump restarted (third detection), the units and the pumps will come to an abnormal stop, and the error code 2519 will
appear.
Detail codes: 201(Pw1), 202(Pw2), 203(Pw3), 204(Pw4)
3. Cause, check method and remedy
7-4-10
Error Code [2520]
1. Error code definition
Water pressure rise
2. Error definition and error detection method
1) If the reading of the pressure sensor Pw1 or Pw2 exceeds 900 kPa while Pump 1 is in operation, or the reading of the pressure
sensor Pw3 or Pw4 exceeds 900 kPa while Pump 2 is in operation (first detection), the outdoor units and the pumps will stop,
go into the 3-minute restart delay mode, and then restart.
2) If the pressure reading exceeds 900 kPa again within 10 minutes of the stoppage of the pump and within 2 minutes after the
pump restarted (second detection), the outdoor units and the pumps will stop again, go into the 3-minute restart delay mode,
and then restart.
3) If the pressure reading exceeds 900 kPa again within 10 minutes of the stoppage of the pump and within 2 minutes after the
pump restarted (third detection), the units and the pumps will come to an abnormal stop, and the error code 2520 will appear.
Detail codes: 201(Pw1), 202(Pw2), 203(Pw3), 204(Pw4)
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Clogged strainer
Check the strainer for clogging.
(2)
Insufficient supply-water pressure
Check that the supply-water pressure is in the
range between 0.1 and 0.16 MPa.
(3)
Air-vent failure
1)
Make sure the air vent valves are located in appro-
priate locations. Refer to [8-14-3 Instructions for
the Air Vent Operation].
2)
Vent the air again in accordance with the proce-
dures explained in [8-14-3 Instructions for the Air
Vent Operation].
Cause
Check method and remedy
(1)
Valve block fault
When the LEDs on the control board (VB3a-VB3p)
are lit, check the valve block whose LED is lit for
loose connectors, wiring fault, and proper opera-
tion. When the LEDs described above are not lit,
check all the valve block for proper operation.
(2)
Port address setting error
Check the indoor unit port address settings.
(3)
Deformed water pipe on site
Check the water pipes on site for deformation.
(4)
Pressure sensor fault
Refer to [8-9-1 Pressure Sensor].
0000006452.BOOK 22 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......