[8-10 Troubleshooting Inverter Problems ]
BS_08_L
chapter 8 -
49
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-10-14
Checking the Pump INV Board for Damage (During pump operation)
8-10-15
Checking the Installation Conditions
8-10-16
Solutions for the Main Breaker Trip
Measure the secondary voltage of the main power breaker before checking because the main power breaker may have been
broken.
Items to be checked
Phenomena
Remedy
Operate the outdoor unit and the
HBC.
Wait until the inverter output frequen-
cy is stabilized, and then check the
inverter output voltage.
1)
Overcurrent-related error occurs im-
mediately after the startup of the
pump or during operation of the
pump.
Check code: 4255, 4256
Detail code: 101, 102, 103, 106, 107
a. Check that the results of the
check items in [8-10-11 Checking
the Pump Motor for Ground Fault
and Coil Resistance Problems]
through [8-10-13 Checking the
Pump INV Board for Damage
(Without load)] are OK.
→
If the error persists after sever-
al compressor restarts, go to "b."
b. After the startup of the compres-
sor, check the high and low pres-
sures for a proper differential
pressure. (Water pressure)
If a proper differential pressure
does not exist, replace the pump.
(The pump may be locked.)
2)
After the inverter output voltage is
stabilized, line voltage imbalance of
at least 5% or 5 V occurs.
If line voltage imbalance exists:
<INV/S20>
Replace the INV board.
Items to be checked
Phenomena
Remedy
(1)
Check refrigerant charge.
Overcharge of refrigerant
Return to correct refrigerant
charge.
(2)
Check outdoor unit branch in-
stallation.
The branch approach <500 mm.
Make branch approach >500mm
Is the branch angle < ±15° to horizontal? Make branch angle < ±15°
Items to be checked
Phenomena
Remedy
[1]
Check the breaker capacity.
Use of a non-specified break-
er
Replace it with a specified breaker.
[2]
Perform Meg check between the
terminals on the power terminal
block TB1.
Zero to several ohm, or Meg
failure
Check each part and wiring.
Refer to the following page(s). [8-10-18
Simple Check on Inverter Circuit Compo-
nents]
IGBT module
Rush current protection resistor
Electromagnetic relay
DC reactor
[3]
Turn on the power again and
check again.
1) Main power breaker trip
2) No remote control display
[4]
Turn on the outdoor unit and check
that it operates normally.
1) Operates normally without
tripping the main breaker.
a) The wiring may have been short-circuit-
ed. Search for the wire that short-circuit-
ed, and repair it.
b) If item a) above is not the cause of the
problem, refer to [8-10-2 Checking the
Inverter Board Error Detection Circuit] -
[8-10-10 Checking the Fan Board for
Damage with Load]
2) Main power breaker trip
0000006416.BOOK 49 ページ 2021年10月26日 火曜日 午後5時30分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......