Error Code [4114]
1. Error code definition
Indoor unit fan motor error
2. Error definition and error detection method
When the fan motor output from the indoor unit circuit board is ON and when the rotation speed input from the fan motor cannot
be detected for 30 seconds or more
3. Cause, check method and remedy
7-6-5
Error Code [4115] Detail Code 101, 102
1. Error code definition
Power supply signal sync error
2. Error definition and error detection method
The frequency cannot be determined when the power is switched on.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Fan motor connector contact failure
Check the fan motor connector CNMF for proper connection.
(2)
Indoor unit circuit board failure
Remove the fan motor connector CNMF and check the voltage at the
indoor unit circuit board.
Testing point 1. 280 VDC (Between CNMF1 (+) and CNMF4 (-))
2. 15 VDC (Between CNMF5 (+) and CNMF4 (-))
Replace the indoor unit circuit board if the voltage is abnormal.
If the 4114 error persists after the indoor unit circuit board is replaced,
replace the fan motor as well.
(3)
Fan motor fault
Replace the fan motor if the voltage is normal in step (2) above.
If the 4114 error persists after the fan motor is replaced, replace the in-
door unit circuit board as well.
Cause
Check method and remedy
(1)
Power supply error
Check for an occurrence of a(n) (instantaneous) power failure at the
time of error detection.
Check that the power-supply voltage is 198 V or above (TB01).
Check to see if the power-supply frequency is in the range between 45
and 54 Hz (55 and 64 Hz) (TB01).
Check the power supply voltage waveform for distortion.
(2)
Coil problem
Check for coil burnout.
(L101 and L102 mounted on the PS board)
(3)
Faulty wiring
Check fuse F111, F121 (PS board)
(4)
Wiring failure
Between TB01 and PS board CNAC
Confirm that the voltage at the PS board connector CNAC (2-4 pin) is
198 V or above.
(5)
PS board failure
If none of the items described above is applicable, and if the trouble re-
appears even after the power is switched on again, replace the PS
board.
0000006452.BOOK 28 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......