[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
38
-
chapter 7
BS_07_M
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-18
Error Code [4220] Detail Code 123
1. Error code definition
Voltage boost control error (Detail code 123)(outdoor unit)
2. Error definition and error detection method
When a drop in power supply voltage or a malfunction in the booster circuit is detected
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
7-6-19
Error Code [4220] Detail Code 129
1. Error code definition
Control power supply error (Detail code 129)(outdoor unit)
2. Error definition and error detection method
INV35Y and INV42Y
Detection of insufficient drive voltage for relays on INV board
INV37YC
Detection of insufficient drive voltage for relays on INV board or for IGBT
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Inverter-output-related
items
Refer to the following page(s). [8-10-2 Checking the Inverter Board Error Detection
Circuit]
Refer to the following page(s). [8-10-3 Checking the Compressor for Ground Fault
and Coil Resistance Problems]
Refer to the following page(s). [8-10-4 Checking the Inverter for Damage at No-
Load]
Refer to the following page(s). [8-10-5 Checking the Inverter for Damage during
Compressor Operation]
Refer to the following page(s). [8-10-15 Checking the Installation Conditions]
Cause
Check method and remedy
(1)
Contact failure
<INV35Y and INV42Y>
Check the connectors CNRY on INV board and CNRYA on MAIN board for proper
connections.
<INV37YC>
Check the connectors CNRY on INV board and CNRYA on MAIN board for proper
connections.
Check the connectors CN200 on INV board and CN300 on PS board for proper con-
nections.
(2)
Voltage check
Disconnect the connector CNRYA from the control board and check the voltage at
the connector CNRYA. If a voltage of 13 V is not output, replace the control board
and the PS board.
(3)
Inverter board failure
If the problem persists after reboot, replace the INV board.
0000006452.BOOK 38 ページ 2021年10月27日 水曜日 午前9時38分
Summary of Contents for City Multi PURY-EM200YNW-A1
Page 1: ......
Page 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Page 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Page 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Page 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Page 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Page 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Page 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Page 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Page 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Page 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Page 502: ......