8. FAN AND ALARM TESTS
GENERAL
This section contains detailed level procedures for fan and alarm tests.
Master control center (MCC) display Page 105/106 is used to summarize building/power alarm status, to provide
inhibit/allow controls for building alarms, and to provide controls for alarm retire mode.
When an alarm condition is present and it is not inhibited, the respective display indicator will backlight, except the
FIRE indicator. The FIRE indicator flashes in addition to the backlighting. In the SUMMARY STATUS AREA, the
associated alarm level (CRITICAL, MAJOR, or MINOR) will backlight, and BLDG/PWR will start flashing. Also, an
audible alarm will sound.
When an alarm is inhibited, the respective indicator will have "INH" written in and will be backlighted; BLDG INH in
the SUMMARY STATUS AREA will also backlight.
Building alarms 02-27 are the only alarms on MCC display Page 105/106 which can be inhibited by the craft. Any
other inhibit present would be the result of a system inhibit.
The indicator near the top right-hand portion of MCC display Page 105/106 shows the retire mode (MANUAL or
AUTOMATIC). Manual mode requires craft action (depressing the alarm retire key on the MCC) to stop CRITICAL
and MAJOR alarms from flashing and to shut off the audible alarms. Automatic mode stops the flashing and shuts
off the audible alarms after 5 seconds.
235-105-210
October 1999
Copyright © 1999
Page 1
Summary of Contents for 5ESS-2000
Page 96: ...235 105 210 October 1999 Copyright 1999 Page 2 ...
Page 184: ...235 105 210 October 1999 Copyright 1999 Page 3 ...
Page 300: ...13 STOP YOU HAVE COMPLETED THIS PROCEDURE 235 105 210 October 1999 Copyright 1999 Page 55 ...
Page 339: ...7 STOP YOU HAVE COMPLETED THIS PROCEDURE 235 105 210 October 1999 Copyright 1999 Page 13 ...
Page 342: ...235 105 210 October 1999 Copyright 1999 Page 2 ...
Page 359: ...235 105 210 October 1999 Copyright 1999 Page 5 ...
Page 609: ...2 STOP YOU HAVE COMPLETED THIS PROCEDURE 235 105 210 October 1999 Copyright 1999 Page 12 ...
Page 676: ...235 105 210 October 1999 Copyright 1999 Page 9 ...
Page 792: ...3 STOP YOU HAVE COMPLETED THIS PROCEDURE 235 105 210 October 1999 Copyright 1999 Page 9 ...
Page 799: ...Figure 11 36 3 1 Cleaning Points 235 105 210 October 1999 Copyright 1999 Page 7 ...
Page 801: ...235 105 210 October 1999 Copyright 1999 Page 9 ...
Page 839: ...2 STOP YOU HAVE COMPLETED THIS PROCEDURE 235 105 210 October 1999 Copyright 1999 Page 16 ...
Page 999: ...2 STOP YOU HAVE COMPLETED THIS PROCEDURE 235 105 210 October 1999 Copyright 1999 Page 13 ...
Page 1008: ...Figure 11 55 1 CTSNS DIP Switch Settings 235 105 210 October 1999 Copyright 1999 Page 2 ...
Page 1011: ...235 105 210 October 1999 Copyright 1999 Page 5 ...
Page 1053: ...235 105 210 October 1999 Copyright 1999 Page 15 ...
Page 1289: ...Figure 15 17 2 AMATPS Data Link 235 105 210 October 1999 Copyright 1999 Page 2 ...
Page 1292: ...235 105 210 October 1999 Copyright 1999 Page 5 ...
Page 1303: ...9 STOP YOU HAVE COMPLETED THIS PROCEDURE 235 105 210 October 1999 Copyright 1999 Page 2 ...
Page 1360: ...Figure 15 47 2 Typical SCANS III Link Diagram 235 105 210 October 1999 Copyright 1999 Page 2 ...
Page 1372: ...235 105 210 October 1999 Copyright 1999 Page 2 ...
Page 1374: ...235 105 210 October 1999 Copyright 1999 Page 4 ...
Page 1421: ...Table 1 1 O M Checklist 235 105 210 October 1999 Copyright 1999 Page 3 ...