The behavior of the auto-off timer can be modified with the property
Auto_Off_Mode
. If
Auto_Off_Mode
is set to ENABLE_RESTART or ENABLE_RESTART_BREAK, the
auto-off timer can be restarted by a new ON command (see Figure 230). If
Auto_Off_Mode
is set ENABLE_BREAK or ENABLE_RESTART_BREAK the auto-off timer can be
stopped before the time has expired by switching the light off via the corresponding
Present_Value
property (see Figure 231).
Figure 230: Timing Parameters (restart enabled).
Figure 231: Timing Parameters (break enabled).
8.3.3.4 Feedback
The DALI lamp, group and channel each report the current state via the
Present_Value
of a
feedback Analog Input (see Section 8.3.3.11).
All Analog Output objects report if they are in manual override mode by setting the
OVERRIDDEN flag in the
Status_Flags
property.
8.3.3.5 Emergency Lights
The following additional, emergency light related properties are available via the Channel
Health Analog Input object (see Section 8.3.3.14):
Battery_Failure
: Report battery failure for each emergency light ballast.
Function_Test_Failure
: Report whether last function test failed for each emergency
light ballast.
Duration_Test_Failure
: Report whether last function test failed for each emergency
light ballast.