is. This allows to quickly change selected values (e.g. button function) for multiple button
objects.
If DALI buttons are used with Constant Light Controller applications to allow manual and
automatic operation please see Section 8.2.8.9 (L
ON
M
ARK
) and 8.3.5.8 (BACnet) on how
DALI buttons can interact with the Constant Light Controller application.
Depending on the selected objects the following special functions (5) are available:
Lamp Actuators
: Reset run hours and Energy Count
Light Sensors
: Calibrate light sensor
Constant Light Controllers
: Calibrate constant light controller
Sunblind Controllers
: Modify sunblind controller event priorities, link sunblind
controller to constant light controller
7.6.1 Reset Run Hours and Energy Count
To reset the run hours and/or energy count of a lamp actuator click on the
Reset Run
Hours/Energy Count…
button. A dialog is displayed which allows you to specify what
you want to reset (see Figure 155).
Figure 155: Reset Run Hours and Energy Count
7.6.2 Calibrate Light Sensor
To calibrate the light sensor click on the
Calibrate Light Sensor …
button. The dialog
shown in Figure 156 is opened.
Figure 156: Light Sensor Calibration
To counter any non-linearity the sensor can be calibrated for up to seven different daylight
illumination levels. However, in most cases it is sufficient to calibrate the sensor only once.
The best result is achieved if the illumination level is near the setpoint. To calibrate the
sensor perform the following steps:
1.
Measure the current lux level at the reference area (e.g. desk) using a luxmeter.
2.
Enter the measured lux level in the input field
Measured Lux Level
.