L-DALI User Manual
334
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Present_Value (Read-Only)
This property reports the percentage of failed ballasts on the corresponding group/channel.
A ballast failure is reported if either
The bus power for the related DALI channel fails,
the DALI ballast is not reachable via the DALI channel, or
the DALI ballast reports a failure (e.g. lamp failure) in its DALI status register.
Status_Flags (Read-Only)
Of the four flags the flags IN_ALARM, FAULT, and OUT_OF_SERVICE are linked to the
state of the corresponding properties
Event_State
,
Reliability
and
Out_Of_Service
as
described by the standard.
OVERRIDDEN
Always FALSE.
Reliability (Read-Only)
The
Reliability
property for this object type may have any of the following values:
NO_FAULT_DETECTED
No fault was detected.
Units (Read-Only)
The value of this property is 98 (percent).
Min_Pres_Value (Read-Only)
The value of this property is 0.
Max_Pres_Value (Read-Only)
The value of this property is 100.
Profile_Name (Read-only)
This property has the following values:
DALI groups: “
178-http://www.loytec.com/xsd/DALIGroupActuatorStatus/v1
”
DALI channels: “
178-http://www.loytec.com/xsd/DALIChannelActuatorStatus/v1
”
Device_Failure (Read-Only)
The value of this proprietary property (property ID 529) is a 64-bit wide BIT STRING. It
contains one bit for each ballast on the channel. If the device fails (offline or failure
reported via DALI status bits) the bit is set, otherwise it is cleared.
Only present if the object is associated with a DALI channel.
Ballast_Failure (Read-Only)
The value of this proprietary property (property ID 530) is a 64-bit wide BIT STRING. It
contains one bit for each ballast on the channel. If the device reports a ballast failure the bit
is set, otherwise it is cleared.