LOYTEC electronics GmbH
5.
In the
Manage Trigger Conditions
list put a check mark on alarm conditions that shall
invoke the transmission of the e-mail.
6.
Change to the
Common E-Mail Properties
tab.
7.
Add the alarm data point as a data source as described in Section 7.10.1.
8.
Choose the desired alarm information from the fields in the drop-down
Selected Data
Source Value
and paste a place holder into the e-mail text or subject field.
7.12.4 Create an Alarm Log
The alarm objects on the device contain an alarm summary (live list) of currently active and
acknowledge-pending alarms. As soon as an alarm becomes inactive and has been
acknowledged, it disappears from the alarm summary. To store a historical log of alarm
transitions an
alarm log
needs to be created.
An alarm log can log transitions of one or more alarm objects. Its size is configurable. The
alarm log can be operated as ring or as linear buffer. When operated as ring buffer, the
oldest alarm log records are overwritten by new alarm transitions, as soon as its size limit is
reached. When operated as linear buffer no more alarms are logged once the log is full.
To Create an Alarm Log
1.
Under the
Global Objects
folder, select the
Alarm Log Object Configuration
sub-
folder.
2.
In the data point list right-click and select
New Alarm Log …
from the context menu.
3.
In the
New Alarm Log
dialog enter a
Name
for the alarm log. Optionally enter a
Description
.