L-DALI User Manual
262
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nciDebounce
Type
SCPTdebounce (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
0 sec
Description
Debouncing time to generate the detection envelope for occupancy detection and the OCCUPIED
and NON OCCUPIED message.
nciUnoccupValue
Type
UCPTunoccupiedValue (SNVT_occupancy)
Valid Range
OC_NUL (-1):
Invalid Value
OC_OCCUPIED (0):
Area is occupied
OC_UNOCCUPIED (1):
Area is unoccupied
OC_BYPASS (2):
Area is temporarily occupied for the bypass period
OC_STANDBY (3):
Area is temporarily unoccupied
Default Value
OC_UNOCCUPIED
Description
This configuration property defines what value is transmitted via
nvoOccup
when the sensor
detects that the room is unoccupied.
nciOccupValue
Type
UCPToccupiedValue (SNVT_occupancy)
Valid Range
OC_NUL (-1):
Invalid Value
OC_OCCUPIED (0):
Area is occupied
OC_UNOCCUPIED (1):
Area is unoccupied
OC_BYPASS (2):
Area is temporarily occupied for the bypass period
OC_STANDBY (3):
Area is temporarily unoccupied
Default Value
OC_ OCCUPIED
Description
This configuration property defines what value is transmitted via
nvoOccup
when the sensor
detects that the room is occupied.
nciUnoccupDly
Type
UCPTunoccupDly (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
0s means disabled (no delay)
Default Value
0 sec
Description
This configuration property specifies the delay after which
nvoOccup
adopts the unoccupied
value. The timer is started when the occupancy sensor detects that the room is unoccupied
8.2.8 Constant Light Controller Object #3050
The L-DALI provides 16 constant light controller objects with built in occupancy controller
functionality for each DALI channel.