![LOYTEC L-DALI User Manual Download Page 185](http://html1.mh-extra.com/html/loytec/l-dali/l-dali_user-manual_1943336185.webp)
L-DALI User Manual
185
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Figure 168: Create Client Mapping Dialog.
3.
Select the tab
Client Mapping
.
4.
Choose a target device in the list of known devices. Enter a
Data Point Name
, choose
an
Object Type
, and edit the target object instance number. Then select the
Mapping
Type
. For read client mappings edit the
COV expiry
or
Pollcycle
setting. For write
client maps edit the
Write Priority
. For value client maps edit both. When finished
click
Create Client Mapping
.
7.8.5 Create Server Object
On the BACnet port server objects can also be created manually. These BACnet objects are
visible on the BACnet network and can be modified by other devices. They appear as data
points in the
BACnet/Datapoints
folder.
To Create Server Objects Manually
1.
Select the
User
sub-folder of the
Datapoints
folder under the
BACnet Port
folder.
2.
Right-click in the data point list and select
New Datapoint…
in the context menu. This
opens the
Create New BACnet Point
dialog as shown in Figure 169.
3.
In the
Mandatory Properties
enter a
Datapoint Name
and an
Object Type
.
Optionally, update the
Instance No
and select the
Commandable
check box for value
objects, if the value object shall be commandable from the network.
4.
In the
Optional Properties
you may select
Engineering Units
for analog objects. For
all object types you can enter the
Description
. The
Device Type
can be left empty. For
multi-state objects you have to select a multi-state map.
5.
Click
Create Server Object
. The BACnet data point is created and appears in the data
point list.