L-DALI User Manual
285
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Priority
Event
Description
14
Frost condition*
The sunblind controller enters the frost state if the network variable input
nviFrost
is active. When
nviFrost
becomes inactive the sunblind
controller remains in the frost state for the hold time configured in
nciRainFroOffDly
.
The sunblind does not move as long as the sunblind controller is in the
frost state.
13
Wind*
The sunblind controller enters the wind alarm state if the measured wind
speed (
nviWind
) exceeds the threshold configured in
nciWindLimit
.
When the wind speed falls below the threshold the sunblind controller
remains in the wind alarm state for the hold time configured in
nciWindOffDly
.
The sunblind remains open while the sunblind controller is in the wind
alarm state.
12
Rain condition*
The sunblind controller enters the rain state if the network variable input
nviRain
is active. When
nviRain
becomes inactive the sunblind controller
remains in the rain state for the hold time configured in
nciRainFroOffDly
.
The sunblind remains open while the sunblind controller is in the rain
state.
11
Set override request
The network variable input
nviSetOverride
is active (.function
!=SET_NUL). See Section 8.2.9.5 for detail.
10
Override request
The network variable input
nviSBOverride
is switched on. The sunblind
drives to the position specified in
nciOverrideValue.
See Section 8.2.9.5
for detail.
9
Window open*
The window is open: The network variable input
nviWindowContact
is
active. The polarity of the window contact can be changed via the
configuration property
nciInvWinCon
.
The sunblind does not move as long as the window is open.
8
Local control
The network variable input
nviLocalControl
is active. See Section
8.2.9.4 for detail.
7
Group control
The network variable input
nviGroupControl
is active. See Section
8.2.9.4 for detail.
6
Global control
The network variable input
nviGlobalControl
is active. See Section
8.2.9.4 for detail.
5
Scene selection
Sunblind scene recalled via network variable input
nviScene
. See Section
8.2.9.4 for detail.
4
Anti-glare*
The sunblind is controlled by the anti-glare algorithm. Only active if
room is occupied. See Section 8.2.9.1 for detail.
3
View protection*
The sunblind is controlled by the view protection algorithm. Only active
if room is occupied. See Section 8.2.9.2 for detail.
2
Constant light request*
The sunblind is linked to the constant light controller and is controlled
by the museum mode algorithm. Only active if room is occupied. See
Section 8.2.8.11 for detail.
1
Up if occupied*
The room is occupied. See Section 8.2.9.8 for detail.
If the room is occupied the sunblind moves up.
0 (lowest)
Heat/cool request*
The sunblind is controlled by the heating/cooling algorithm. Only active
if room is not occupied. See Section 8.2.9.3 for detail.
Table 25: Sunblind Controller Events and Priority
For events marked with *) a minimum time can be configured via the configuration property
nciAutoEvMinTm
. These events will stay active for at least the configured time even if the
event condition disappears before this time expires. In this way the sunblind controller
ensures that the sunblind does not drive too frequently.