LOYTEC electronics GmbH
9 Network Media
9.1 FT (LDALI-10X only)
The L-DALI FT port is fully compatible to the parameters specified by L
ON
M
ARK
for this
channel. FT ports can also be used on Link Power (LP-10) channels. However, the L-DALI
does not provide the power supply for Link Power channels.
When using the Free Topology Segment feature of the FT, only one termination (Figure
246) is required and can be placed anywhere on the free topology segment. Instead of
building the termination, one can order the L-Term module (LT-33) from LOYTEC, which
can be used to properly terminate the bus.
+
+
100 µF, 50V
100 µF, 50V
52,3
Figure 246: FT Free Topology Termination
In a double terminated bus topology, two terminations are required (Figure 247). These
terminations need to be placed at each end of the bus. Here, also L-Term modules can be
used at either end.
+
+
100 µF, 50V
100 µF, 50V
105
100 µF, 50V
+
105
100 µF, 50V
+
Figure 247: Termination in an FT Bus Topology